Pepperl+Fuchs KFD2-UT2-2
Universal Temperature Converter
We ship to United States of America!
- 2-channel signal conditioner
- 24 V DC supply (Power Rail)
- Thermocouple, RTD, potentiometer or voltage input
- Usable as signal splitter (1 input and 2 outputs)
- Current output 0/4 mA ... 20 mA
- Sink or source mode
- Configurable by PACTware
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number:
KFD2-UT2-2
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
Connection | terminals 1, 2, 3; 4, 5, 6 |
Degree of protection | IP20 |
Configuration | via PACTware |
Connection | terminals 14+, 15- or power feed module/Power Rail |
Ripple | within the supply tolerance |
Voltage | selectable within the range -100 ... 100 mV |
Safety Integrity Level (SIL) | SIL 2 |
Degree of protection | IEC 60529:2001 |
Connection side | control side |
Mass | approx. 130 g |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Signal type | Analog input |
Programming interface | programming socket |
Output I, II | Analog current output |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Electromagnetic compatibility | NE 21:2006 |
Connection | screw terminals |
Rated voltage | 20 ... 30 V DC |
Input resistance | 1 MandOmega; (-100 ... 100 mV) |
Labeling | space for labeling at the front |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
Input/Other circuits | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Power dissipation/power consumption | 1.53 W / 1.53 W |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Connection side | field side |
Potentiometer | 0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection) |
Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) |
Display elements | LEDs |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
Buy Pepperl+Fuchs KFD2-UT2-2 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. offers electrical products online. We offer a comprehensive range of reliable and high-efficiency products. Express delivery is available to all our clients. We offer only original products from well-known manufacturers. If you need the products very urgently, we will do our best to provide you with the fastest delivery. We have a lot of positive feedback from our clients and partners, we are recommended!