Pepperl+Fuchs KFD2-UT2-2-1
Universal Temperature Converter

Pepperl+Fuchs KFD2-UT2-2-1
  • 2-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Usable as signal splitter (1 input and 2 outputs)
  • Voltage output 0/1 V ... 5 V
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KFD2-UT2-2-1
525.02
-
+
Total price: 525.02
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Voltage output0 ... 5 V or 1 ... 5 V ; output resistance: 5 andOmega; ; load: 10 kandOmega;

Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Degree of protectionIEC 60529:2001
Labelingspace for labeling at the front
Fault signaldownscale 0 V or 0.5 V, upscale 5.375 V
Signal typeAnalog input
Voltageselectable within the range -100 ... 100 mV
Rated voltage20 ... 30 V DC
Connectionterminals 14+, 15- or power feed module/Power Rail
Connectionscrew terminals
Input resistance1 MandOmega; (-100 ... 100 mV)
Connectionoutput I: terminals 7-, 8+
output II: terminals 10-, 11+
Electromagnetic compatibilityNE 21:2006
Power dissipation/power consumption0.8 W / 0.8 W
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Connection sidefield side
Safety Integrity Level (SIL)SIL 2
Connection sidecontrol side
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Programming interfaceprogramming socket
Connectionterminals 1, 2, 3; 4, 5, 6
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Configurationvia PACTware
Massapprox. 130 g
Ripplewithin the supply tolerance
Display elementsLEDs
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Degree of protectionIP20
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Potentiometer0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)

Comments

No comments yet