Pepperl+Fuchs KFD2-UT2-2-1
Universal Temperature Converter

Pepperl+Fuchs KFD2-UT2-2-1
We ship to United States of America!
  • 2-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Usable as signal splitter (1 input and 2 outputs)
  • Voltage output 0/1 V ... 5 V
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KFD2-UT2-2-1
525.02
-
+
Total price: 525.02
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Voltage output0 ... 5 V or 1 ... 5 V ; output resistance: 5 andOmega; ; load: 10 kandOmega;

Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Degree of protectionIEC 60529:2001
Labelingspace for labeling at the front
Fault signaldownscale 0 V or 0.5 V, upscale 5.375 V
Signal typeAnalog input
Voltageselectable within the range -100 ... 100 mV
Rated voltage20 ... 30 V DC
Connectionterminals 14+, 15- or power feed module/Power Rail
Connectionscrew terminals
Input resistance1 MandOmega; (-100 ... 100 mV)
Connectionoutput I: terminals 7-, 8+
output II: terminals 10-, 11+
Electromagnetic compatibilityNE 21:2006
Power dissipation/power consumption0.8 W / 0.8 W
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Connection sidefield side
Safety Integrity Level (SIL)SIL 2
Connection sidecontrol side
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Programming interfaceprogramming socket
Connectionterminals 1, 2, 3; 4, 5, 6
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Configurationvia PACTware
Massapprox. 130 g
Ripplewithin the supply tolerance
Display elementsLEDs
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Degree of protectionIP20
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Potentiometer0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)

Buy Pepperl+Fuchs KFD2-UT2-2-1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. offers electrical supplies online. We offer 50+ automation equipment brands. For your convenience, we can arrange express delivery worldwide. Guaranteed quality with the minimum possible prices. You don't need to pay in advance if you are our regular customer. Ordering from us you will get convenience and high speed of purchase.

Comments

No comments yet

Write a comment