Pepperl+Fuchs KFD2-UT2-2-1
Universal Temperature Converter
We ship to United States of America!
- 2-channel signal conditioner
- 24 V DC supply (Power Rail)
- Thermocouple, RTD, potentiometer or voltage input
- Usable as signal splitter (1 input and 2 outputs)
- Voltage output 0/1 V ... 5 V
- Configurable by PACTware
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number:
KFD2-UT2-2-1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Voltage output0 ... 5 V or 1 ... 5 V ; output resistance: 5 andOmega; ; load: 10 kandOmega;
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Degree of protection | IEC 60529:2001 |
Labeling | space for labeling at the front |
Fault signal | downscale 0 V or 0.5 V, upscale 5.375 V |
Signal type | Analog input |
Voltage | selectable within the range -100 ... 100 mV |
Rated voltage | 20 ... 30 V DC |
Connection | terminals 14+, 15- or power feed module/Power Rail |
Connection | screw terminals |
Input resistance | 1 MandOmega; (-100 ... 100 mV) |
Connection | output I: terminals 7-, 8+ output II: terminals 10-, 11+ |
Electromagnetic compatibility | NE 21:2006 |
Power dissipation/power consumption | 0.8 W / 0.8 W |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Connection side | field side |
Safety Integrity Level (SIL) | SIL 2 |
Connection side | control side |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
Programming interface | programming socket |
Connection | terminals 1, 2, 3; 4, 5, 6 |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
Configuration | via PACTware |
Mass | approx. 130 g |
Ripple | within the supply tolerance |
Display elements | LEDs |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
Degree of protection | IP20 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Potentiometer | 0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection) |
Buy Pepperl+Fuchs KFD2-UT2-2-1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. offers electrical supplies online. We offer 50+ automation equipment brands. For your convenience, we can arrange express delivery worldwide. Guaranteed quality with the minimum possible prices. You don't need to pay in advance if you are our regular customer. Ordering from us you will get convenience and high speed of purchase.
People also buy
Comments
No comments yet