Pepperl+Fuchs KFD2-UT2-Ex1
Universal Temperature Converter

Pepperl+Fuchs KFD2-UT2-Ex1
We ship to United States of America!
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Thermocouple, RTD, potentiometer or voltage input

Item Number: KFD2-UT2-Ex1
400.98
-
+
Total price: 400.98
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
  • Overview +
  • Comments +
  • CertificateT??V 02 ATEX 1797 X

  • Current output 0/4 mA ... 20 mA

  • Sink or source mode

  • Configurable by PACTware

  • Line fault (LFD) and sensor burnout detection

  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Voltage

selectable within the range -100 ... 100 mV

Dimensions

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2

Connection

screw terminals

Programming interface

programming socket

Rated voltage

20 ... 30 V DC

Configuration

via PACTware

Output

Analog current output

Connection side

field side

RTD

type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)

type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)

type Cu10, Cu50, Cu100 (P50353-92)

type Ni100 (DIN 43760)

Potentiometer

0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)

Thermocouples

type B, E, J, K, N, R, S, T (IEC 584-1: 1995)

type L (DIN 43710: 1985)

type TXK, TXKH, TXA (P8.585-2001)

Connection side

control side

Connection

terminals 1, 2, 3, 4

Ripple

within the supply tolerance

Display elements

LEDs

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Degree of protection

IEC 60529:2001

Input resistance

1 MandOmega; (-100 ... 100 mV)

Connection

output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)

Mass

approx. 130 g

Connection

terminals 14+, 15- or power feed module/Power Rail

Safety Integrity Level (SIL)

SIL 2

Labeling

space for labeling at the front

Signal type

Analog input

EU-Type Examination Certificate

CESI 04 ATEX 143

Degree of protection

IP20

Electromagnetic compatibility

NE 21:2006

Power dissipation/power consumption

0.98 W / 0.98 W

Ambient temperature

-20 ... 60 ?°C (-4 ... 140 ?°F)

Reaction time

worst case value (sensor breakage and/or sensor short circuit detection enabled)

mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s


Buy Pepperl+Fuchs KFD2-UT2-Ex1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is fast developing company in automation instrumentation. Due to a wide range of brands, we allow you to refuse many other suppliers greatly saving your time. We provide delivery all over the world. We will help you to save money with our lowest prices. We are keeping you up-to-date with Tracking Numbers throughout the process. We always fulfill our obligations.

Comments

No comments yet

Write a comment