Pepperl+Fuchs KFD2-UT2-Ex1-1
Universal Temperature Converter
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Thermocouple, RTD, potentiometer or voltage input
- Voltage output 0/1 V ... 5 V
- Configurable by PACTware
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number:
KFD2-UT2-Ex1-1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
CertificateT??V 02 ATEX 1797 X
Power dissipation/power consumption | 0.64 W / 0.64 W |
Rated voltage | 20 ... 30 V DC |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
Mass | approx. 130 g |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection side | control side |
Ripple | within the supply tolerance |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Safety Integrity Level (SIL) | SIL 2 |
Connection side | field side |
Protection against electrical shock | UL 61010-1:2004 |
Voltage output | 0 ... 5 V or 1 ... 5 V ; output resistance: 5 andOmega; ; load: 10 kandOmega; |
Connection | screw terminals |
Signal type | Analog input |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Inputs | terminals 1, 2, 3, 4 |
Voltage | selectable within the range -100 ... 100 mV |
Programming interface | programming socket |
Connection | terminals 14+, 15- or power feed module/Power Rail |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - FDT framework PACTware 4.1 - device type manager DTM Interface Technology - adapter K-ADP-USB-AB |
Labeling | space for labeling at the front |
Connection | terminals 7-, 8+ |
Fault signal | downscale 0 V or 0.5 V, upscale 5.375 V |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Input resistance | 1 MandOmega; (-100 ... 100 mV) |
Degree of protection | IEC 60529:2001 |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
Potentiometer | 0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection) |
Configuration | via PACTware |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Degree of protection | IP20 |
EU-Type Examination Certificate | CESI 04 ATEX 143 |
Electromagnetic compatibility | NE 21:2006 |
Connection | terminals 1, 2, 3, 4 |
Display elements | LEDs |
Buy Pepperl+Fuchs KFD2-UT2-Ex1-1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. is fast developing company in supplying industrial automation equipment. Our product range spreads from simple electronic components and switches to high-voltage complex systems. We supply equipment in Europe and throughout the world. The quality of the products we carry meets all international standards and the price is minimal compared to our competitors. We will keep You informed at all stages of the deal. We adhere to the principle of winβwin, and our purpose is mutually advantageous long-term cooperation.
People also buy
Comments