Pepperl+Fuchs KFD2-UT2-Ex2-1
Universal Temperature Converter

Pepperl+Fuchs KFD2-UT2-Ex2-1
We ship to United States of America!
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Usable as signal splitter (1 input and 2 outputs)
  • Voltage output 0/1 V ... 5 V
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KFD2-UT2-Ex2-1
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Massapprox. 130 g
Potentiometer0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)
Signal typeAnalog input
Safety Integrity Level (SIL)SIL 2
Rated voltage20 ... 30 V DC
Display elementsLEDs
Connectionscrew terminals
Power dissipation/power consumption 0.8 W / 0.8 W
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Voltageselectable within the range -100 ... 100 mV
Inputsterminals 1, 2, 3, 4, 5, 6 (for passive equipment)
Labelingspace for labeling at the front
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connectionterminals 1, 2, 3; 4, 5, 6
Input resistance 1 MandOmega; (-100 ... 100 mV)
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Connectionterminals 14+, 15- or power feed module/Power Rail
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connection sidefield side
Fault signaldownscale 0 V or 0.5 V, upscale 5.375 V
Connection sidecontrol side
CertificateT??V 02 ATEX 1797 X
EU-Type Examination CertificateCESI 04 ATEX 143
Connectionoutput I: terminals 7-, 8+
output II: terminals 10-, 11+
Electromagnetic compatibilityNE 21:2006
Configurationvia PACTware
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Voltage output0 ... 5 V or 1 ... 5 V ; output resistance: 5 andOmega; ; load: 10 kandOmega;
Degree of protectionIEC 60529:2001
Ripplewithin the supply tolerance
Degree of protectionIP20
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- FDT framework PACTware 4.1
- device type manager DTM Interface Technology
- adapter K-ADP-USB-AB
Programming interfaceprogramming socket
Protection against electrical shockUL 61010-1:2004

Buy Pepperl+Fuchs KFD2-UT2-Ex2-1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade is a known electrical equipment supplier. We offer a wide range of electronic automation products. We ship to any location in the world. We can offer you competitive prices for all items from our web catalog and Eltra Trade is always on time with the delivery time. We have the best ratio of speed, product quality and price.

Comments

No comments yet

Write a comment