Pepperl+Fuchs KFD2-VR2-Ex1.50M
Voltage Repeater

Pepperl+Fuchs KFD2-VR2-Ex1.50M
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

Item Number: KFD2-VR2-Ex1.50M
364.00
-
+
Total price: 364.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
  • Voltage-50 ... 50 mV

  • Voltage input 0 mV ... В± 50 mV

  • Voltage output 0 mV ... В± 50 mV

  • Selectable up/downscale sensor breakage detection

EU-Type Examination Certificate

BASEEFA 06 ATEX 0040

Display elements

LED

Dimensions

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2

Degree of protection

IEC 60529

Connection

terminals 7+, 8-

Certificate

BASEEFA 09 ATEX 0219X

Protection against electrical shock

UL 61010-1

Ripple

within the supply tolerance

Optional accessories

- power feed module KFD2-EB2(.R4A.B)(.SP)

- universal power rail UPR-03(-M)(-S)

- profile rail K-DUCT-BU(-UPR-03)

Cut-off frequency

350 Hz (-3 dB)

Transmission range

-50 ... 50 mV

Configuration

via DIP switches

Connection

screw terminals

Line fault detection

100 nA

Offset voltage/current

5 andmicro;V / 5 nA

Output/power supply

functional insulation, rated insulation voltage 50 V AC

Connection

Power Rail or terminals 14+, 15-

Connection

terminals 4+, 5-

Input resistance

min. 20 MandOmega;

Load

Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kandOmega;

Power dissipation/power consumption

0.3 W max.

Output resistance

max. 3 andOmega;

Connection side

field side

Signal type

Analog input

Supplementary information

Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Connection side

control side

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Rise time

1 ms

Ambient temperature

-20 ... 60 В°C (-4 ... 140 В°F)

Electromagnetic compatibility

NE 21

Rated current

11 mA

Labeling

space for labeling at the front

Absolute

< 0.25 K at 30 V voltage supply

Rated voltage

19 ... 30 V DC

Control elements

DIP-switch

Degree of protection

IP20

Fault signal

sensor breakage: > +100 mV (upscale), < -100 mV (downscale)

Mass

approx. 125 g

Comments

No comments yet