Pepperl+Fuchs KFD2-WAC2-1.D
Strain Gauge Converter
We ship to United States of America!
- 1-channel signal conditioner
- 24 V DC supply (Power Rail)
- Strain gauge input (full or half bridge)
- Output 0 mA ... ?± 20 mA or 0 V ... ?± 10 V
- 2 relay contact outputs
- Programmable high/low alarm
- Configurable by PACTware or keypad
- RS-485 interface
- Line fault detection (LFD)
Item Number:
KFD2-WAC2-1.D
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Connectionterminals 1+, 2-, 3+, 4-, 5+, 6-
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Degree of protection | IEC 60529:2001 |
Rated voltage | 20 ... 35 V DC |
UL approval | E223772 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Configuration | via operating buttons via PACTware |
Control elements | Control panel |
Power consumption | max. 3 W |
Input I | Signal, analog |
Ripple | within the supply tolerance |
Output III/Input II, III | not available |
Connection | screw terminals |
Connection side | field side |
Line fault detection | downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V) |
Degree of protection | IP20 |
Collective error message | Power Rail |
Reaction time | 300 ... 850 ms |
Connection side | control side |
Output I, II | Relay output |
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Connection | Input I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14- |
Electromagnetic compatibility | NE 21:2006 |
Lead resistance | max. 25 andOmega; per line |
Display elements | LEDs , display |
Mass | approx. 250 g |
Output III/Programming socket | not available |
Connection | Power Rail or terminals 19+, 20 GND, 21- |
Programmable Tare | 0 ... 500 % of span |
Input II, III | tare adjustment, calibration and zero |
Type | RS-485 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Labeling | space for labeling at the front |
Signal type | Analog input |
Connection | Power Rail or terminals 23+, 24- |
Other circuits from each other | functional insulation, rated insulation voltage 50 Veff |
Sensor supply | 1 ... 5 V |
Programming interface | programming socket |
Connection | Output I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8+, 9- |
Output III | Analog output |
Buy Pepperl+Fuchs KFD2-WAC2-1.D with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com electrical supply online catalog. We offer automation products for any application. We can arrange the fastest supply to any country in the world. We sell only certified parts from European manufacturers. By cooperating with us, you will receive your orders on time. Eltra Trade company is the most reliable and it is very convenient to work with us.