Pepperl+Fuchs KFD2-WAC2-Ex1.D
Strain Gauge Converter
![Pepperl+Fuchs KFD2-WAC2-Ex1.D](https://eltra-trade.com/files/products/pepperl/kfd2-wac2-ex1d.png)
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Strain gauge input (full or half bridge)
- Output 0 mA ... В± 20 mA or 0 V ... В± 10 V
- 2 relay contact outputs
- Programmable high/low alarm
- Configurable by PACTware or keypad
- RS-485 interface
- Line fault detection (LFD)
![](/files/brands/Pepperl+Fuchs-logo-brands.jpg)
Item Number:
KFD2-WAC2-Ex1.D
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Reaction time | 300 ... 850 ms |
Output I, II | Relay output |
Connection | Input I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14- |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Electromagnetic compatibility | NE 21:2006 |
Labeling | space for labeling at the front |
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Line fault detection | downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V) |
Collective error message | Power Rail |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Type | RS-485 |
IECEx approval | IECEx TUN 06.0005 |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Degree of protection | IP20 |
Mass | approx. 250 g |
EU-Type Examination Certificate | TГњV 04 ATEX 2531 |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Output III | terminals 7-, 8+, 9- non-intrinsically safe |
Programming interface | programming socket |
Output III/Programming socket | not available |
Output III | Analog output |
Connection side | field side |
Input I | Signal, analog |
Rated voltage | 20 ... 35 V DC |
UL approval | E223772 |
Lead resistance | max. 25 andOmega; per line |
Ripple | within the supply tolerance |
Connection | Power Rail or terminals 23+, 24- |
Display elements | LEDs , display |
Programmable Tare | 0 ... 500 % of span |
Connection | screw terminals |
Connection | terminals 1+, 2-, 3+, 4-, 5+, 6- |
Output III/Input II, III | not available |
Sensor supply | 1 ... 5 V |
Signal type | Analog input |
Input I | terminals 1+, 2- Ex ia IIC, Ex iaD |
Connection | Power Rail or terminals 19+, 20 GND, 21- |
Input II and III | terminals 13+, 14-; 15+, 14- non-intrinsically safe |
Other circuits from each other | functional insulation, rated insulation voltage 50 Veff |
Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe |
Interface | RS 485 programming jack |
Input II, III | tare adjustment, calibration and zero |
Connection | Output I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8+, 9- |
Configuration | via operating buttons via PACTware |
Control elements | Control panel |
Connection side | control side |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Degree of protection | IEC 60529:2001 |
Power consumption | max. 3 W |
Supply | Power Rail or terminals 23+, 24- non-intrinsically safe |
Buy Pepperl+Fuchs KFD2-WAC2-Ex1.D with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com is an electrical supply store online. We provide an enhanced product catalog for our clients. Rush shipping is available to any country. We supply only certified products from European brands. We always strive to correspond with the delivery times. Our company has a very well-established supply chain so we always provide the equipment on time and without delay.