Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1
Strain Gauge Converter
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Strain gauge input (full or half bridge)
- Output 0 mA ... В± 20 mA or 0 V ... В± 10 V
- 2 relay contact outputs
- Programmable high/low alarm
- Configurable by PACTware or keypad
- RS-485 interface
- Low response time
- Line fault detection (LFD)
Item Number:
KFD2-WAC2-Ex1.D-Y1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connection side | field side |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Output III | terminals 7-, 8+, 9- non-intrinsically safe |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Programming interface | programming socket |
Type | RS-485 |
IECEx approval | IECEx TUN 06.0005 |
Degree of protection | IEC 60529:2001 |
Lead resistance | max. 25 andOmega; per line |
Interface | RS 485 programming jack |
Configuration | via operating buttons via PACTware |
Connection | screw terminals |
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Supply | Power Rail or terminals 23+, 24- non-intrinsically safe |
Input I | Signal, analog |
Electromagnetic compatibility | NE 21:2006 |
Display elements | LEDs , display |
Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe |
Signal type | Analog input |
Output III/Input II, III | not available |
Connection | Power Rail or terminals 19+, 20 GND, 21- |
Control elements | Control panel |
Reaction time | 150 ms |
Sensor supply | 1 ... 5 V |
Connection | terminals 1+, 2-, 3+, 4-, 5+, 6- |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Other circuits from each other | functional insulation, rated insulation voltage 50 Veff |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Line fault detection | downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V) |
Connection | Power Rail or terminals 23+, 24- |
Input II and III | terminals 13+, 14-; 15+, 14- non-intrinsically safe |
Power consumption | max. 3 W |
UL approval | E223772 |
Connection | Input I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14- |
EU-Type Examination Certificate | TГњV 04 ATEX 2531 |
Connection side | control side |
Mass | approx. 250 g |
Output I, II | Relay output |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Ripple | within the supply tolerance |
Collective error message | Power Rail |
Input II, III | tare adjustment, calibration and zero |
Connection | Output I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8+, 9- |
Output III/Programming socket | not available |
Input I | terminals 1+, 2- Ex ia IIC, Ex iaD |
Output III | Analog output |
Degree of protection | IP20 |
Programmable Tare | 0 ... 500 % of span |
Labeling | space for labeling at the front |
Rated voltage | 20 ... 35 V DC |
Buy Pepperl+Fuchs KFD2-WAC2-Ex1.D-Y1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. is an electrical wholesaler online. We offer an enhanced product range of automation products. We can ship your order on the same day. We offer our clients only cost-effective solutions. The main advantage is that we always have a solution for you. Our company has a stable image of one of the best in our field, and we constantly prove it.