Pepperl+Fuchs KFU8-UFC-1.D.FA
Frequency Converter with Trip Values

Pepperl+Fuchs KFU8-UFC-1.D.FA
  • 1-channel signal conditioner
  • Universal usage at different power supplies
  • Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts
  • Input frequency 1 mHz ... 10 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KFU8-UFC-1.D.FA
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

Start-up override/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connection sidefield side
Degree of protectionIEC 60529:2001
Optional accessories- FDT framework PACTware 4.1
- device type manager DTM Interface Technology
- adapter K-ADP-USB
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Power dissipation/power consumption2 W ; 2.5 VA / 2.2 W ; 3 VA
Output IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionterminals 23, 24
Output III/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input I2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Rated voltage20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Control elementsControl panel
Output III/IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Labelingspace for labeling at the front
Degree of protectionIP20
Output IIIelectronic output, passive
Output IVanalog
Mass300 g
ConnectionInput I: 2-wire sensor: terminals 1+, 3- three wire sensor: terminals 1+, 2- and 3
input II: terminals 13+, 14- start-up override;
Safety Integrity Level (SIL)SIL 2
Display elementsLEDs , display
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Signal typeDigital Input
Configurationvia operating buttons
via PACTware
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Input IIstartup override: 1 ... 1000 s, adjustable in steps of 1 s
Output I, IIsignal, relay
Programming interfaceprogramming socket
Connectionscrew terminals
Interface/output IIIbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Connection sidecontrol side
Electromagnetic compatibilityNE 21:2006

Comments

No comments yet

Write a comment