Pepperl+Fuchs KFU8-UFT-Ex2.D
Frequency Converter with Direction and Synchronization Monitor

Pepperl+Fuchs KFU8-UFT-Ex2.D
  • 2-channel isolated barrier
  • Universal usage at different power supplies
  • Dry contact or NAMUR inputs
  • Input frequency 1 mHz ... 1 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Configurable by PACTware or keypad
  • Line fault detection (LFD)
Item Number: KFU8-UFT-Ex2.D
753.00
-
+
Total price: 753.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
InterfaceRS 232
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connectionterminals 23, 24
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Degree of protectionIP20
Power dissipation2.2 W / 3.5 VA
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elementsLEDs , display
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output Vterminals 8+, 7- non-intrinsically safe
Degree of protectionIEC 60529:2001
Output V/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Programming interfaceprogramming socket
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III and IVsignal , electronic output, passive
Input III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input I, II2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Output III and IVterminals 19, 20, 21 non-intrinsically safe
EU-Type Examination CertificateTГњV 99 ATEX 1471
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Signal typeDigital Input
Control elementsControl panel
Input III and IVterminals 13+, 14-; 15+, 14- non-intrinsically safe
Output III, IV/Vbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Connection sidecontrol side
Accuracy0.1 %
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connection sidefield side
IECEx approvalIECEx TUN 04.0007
Connectionscrew terminals
Interface/output III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output I, IIsignal , relay
Labelingspace for labeling at the front
Mass300 g
Rated currentapprox. 130 mA
Output Vanalog
Power consumption2.5 W / 5 VA
Output III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Electromagnetic compatibilityNE 21:2006
Input I and IIterminals 1+, 3-; 4+, 6-: Ex ia
Output III, IV/input III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Input I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Rated voltage20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
InputEN 60947-5-6:2000
Configurationvia operating buttons
via PACTware
Connectioninput I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)

Comments