Pepperl+Fuchs LA28/LK28-FC-Z/31/116
Fire protection thru-beam sensor
- Compact fire protection photoelectric sensor for safety devices on fire barriers
- Approval in accordance with VdS Test Report FSA and externally monitored manufacture (Гњ Symbol)
- Not sensitive to ambient light, even with switched energy saving lamps
Item Number:
LA28/LK28-FC-Z/31/116
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Timer function | ON delay (GAN), OFF delay (GAB), one shot (IAB), ON delay-OFF delay (GAN-GAB), programmable adjustment range 0.1 ...10 s |
Light type | modulated visible red light and modulated infrared light |
Relative humidity | 30% ... 85% non-condensing ; Non-icing |
EAC conformity | TR CU 020/2011 TR CU 004/2011 |
Response time | 20 ms |
Switching type | light/dark on, switchable . (selectable, light/dark switching is only activated if the receiver has 'dark on' selected.) |
Diameter of the light spot | approx. 0.2 m at 10 m |
Ambient temperature | -40 ... 60 В°C (-40 ... 140 В°F) |
Ambient light limit | 50000 Lux |
Angle of divergence | Emitter 1.2В°, Receiver 5В° |
Switching power | DC: max. 50 W AC: max. 500 VA |
Light source | LED, 660 nm and IRED, 880 nm |
CCC approval | Certified by China Compulsory Certification (CCC) |
Approvals | VdS/DIBt certificate of compliance No. 25021 |
Connection | terminal compartment with 8 spring-loaded terminals for wire cross section 0.5 ... 1.5 mm2 , Insulation stripping 7.5 ... 8.5 mm , M16 x 1.5 cable gland |
Alignment aid | LED red (in receiver lens) illuminated constantly: beam is interrupted, flashes: reaching switching point, off: sufficient stability control |
Operation indicator | LED green |
Threshold detection range | 10 m |
Effective detection range | 0 ... 10 m |
Standards | EN 60947-5-2 smoke insensitive up to 2 dB/m ( EN 54-12 ) |
Signal output | Relay, 1 alternator |
Switching voltage | max. 250 V AC/DC |
Switching current | max. 2 A |
Protection class | II, rated insulation voltage 250 V AC with pollution degree 1-2 according to IEC 60664-1 Output circuit insulated from control circuit in accordance with IEC 61140. Caution! The protection class 2 is only valid when the terminal compartment is closed. |
Operating voltage | 12 ... 240 V AC/DC |
Storage temperature | -40 ... 75 В°C (-40 ... 167 В°F) |
Power consumption | 3.5 VA |
Mass | 200 g (emitter and receiver) |
Degree of protection | IP67 |
Control elements | Light-on/dark-on changeover switch ; Time adjuster |
Switching frequency | 25 Hz |
Function indicator | LED yellow: 1. LED lit constantly: signal > 2 x switching point (function reserve) 2. LED flashes: signal between 1 x switching point and 2 x switching point 3. LED off: signal < switching point |
People also buy
Comments
No comments yet