Pepperl+Fuchs LB1009A
Digital Input
We ship to United States of America!
- 8-channel
- Inputs Ex ic
- Installation in Zone 2 or safe area
- Dry contact or NAMUR inputs
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Line fault detection (LFD)
- Permanently self-monitoring
- Module can be exchanged under voltage
Item Number:
LB1009A
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Coding | optional mechanical coding via front socket |
IECEx approval | EXA 13.0003X |
Power consumption | 1.55 W |
Mass | approx. 90 g |
Voltage | 8.2 V |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?± 1 mm/0.7 g; 90 minutes at each resonance |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Connection | backplane bus |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Internal resistor | 1 kandOmega; |
ATEX approval | EXA 13 ATEX 0037X |
Power dissipation | 1.55 W |
Line fault detection | can be switched on/off for each channel via configuration tool , active signals (24 V, 5 V) without line fault detection |
Environmental test | EN 60068-2-14 |
Certificate | EXA 13 ATEX 0037X |
LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel) |
Connection | backplane bus |
Electromagnetic compatibility | NE 21 |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
Degree of protection | IP20 when mounted on backplane |
Minimum pulse duration | 15 ms |
Shock resistance | EN 60068-2-27 |
Degree of protection | IEC 60529 |
Occupied slots | 1 |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Connection | removable front connector with spring terminal (0.14 ... 0.5 mm2) |
Vibration resistance | EN 60068-2-6 |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / ?± 0.2 mA |
Relative humidity | EN 60068-2-56 |
Connection | Terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16- |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
Storage temperature | -25 ... 85 ?°C (-13 ... 185 ?°F) |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) , 70 ?°C (non-Ex) |
Number of channels | 8 |
Damaging gas | EN 60068-2-42 |
Interface | manufacturer-specific bus to standard com unit |
Digital signals (active) | Use in safe area: configurable 24 V 5 V |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Buy Pepperl+Fuchs LB1009A with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com offers an extensive range of industrial electrical products. We specialize in sourcing and delivering hard-to-find parts promptly. Our commitment to quality and competitive pricing makes us a preferred supplier. Partner with us for reliable and efficient electrical supply solutions.
People also buy
Comments
No comments yet