Pepperl+Fuchs LB1102A
Digital Input

Pepperl+Fuchs LB1102A
We ship to United States of America!
  • 3-channel
  • Inputs Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Dry contact or NAMUR inputs
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Module can be exchanged under voltage
Item Number: LB1102A
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Rated valuesacc. to EN 60947-5-6 (NAMUR)
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Connectionbackplane bus
Power dissipation0.75 W
ATEX approvalPF 08 CERT 1234 X PTB 03 ATEX 2042
Relative humidity95 % non-condensing
Vibration resistanceEN 60068-2-6
Switching point/switching hysteresis1.2 ... 2.1 mA / ?± 0.2 mA
Connectionchannel I: 1+, 4-; channel II: 2+, 5-; channel III: 3+, 6-
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?± 1 mm/0.7 g; 90 minutes at each resonance
Power consumption0.75 W
Rated voltage12 V DC , only in connection with the power supplies LB9***
Environmental testEN 60068-2-14
Connectionbackplane bus
Occupied slots1
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Electromagnetic compatibilityNE 21
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Codingoptional mechanical coding via front socket
Degree of protectionIEC 60529
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
CertificatePF 08 CERT 1234 X
Relative humidityEN 60068-2-56
Minimum pulse duration20 ms
LED indicationLED green: supply
LED red: line fault, per channel
LED yellow: signal (status), per channel
IECEx approvalBVS 09.0037X
Shock resistanceEN 60068-2-27
EAC approvalRussia: RU C-IT.MIII06.B.00129
Internal resistor1 kandOmega;
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Line fault detectioncan be switched on/off for each channel via configuration tool
Damaging gasEN 60068-2-42
EU-Type Examination CertificatePTB 03 ATEX 2042
Number of channels3
Voltage8.2 V
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Interfacemanufacturer-specific bus to standard com unit
Massapprox. 90 g
UL approvalE106378
Storage temperature-25 ... 85 ?°C (-13 ... 185 ?°F)

Buy Pepperl+Fuchs LB1102A with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. offers high-quality industrial control products. Our extensive inventory and prompt delivery options ensure you receive your order quickly. We prioritize quality and customer satisfaction. Contact us today to learn more about our offerings.

Comments

No comments yet

Write a comment