Pepperl+Fuchs LB1103A
Frequency / Counter Input

Pepperl+Fuchs LB1103A
We ship to United States of America!
  • 1-channel
  • Input Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Input for frequency, counter, direction of rotation
  • Digital input max. 15 kHz
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Module can be exchanged under voltage
Item Number: LB1103A
417.00
-
+
Total price: 417.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Minimum pulse duration; in frequency + counter mode: 12.5 ms ; otherwise 20 micro/s
Shock resistanceEN 60068-2-27
Number of channels1
ATEX approvalPTB 03 ATEX 2042
Connectionbackplane bus
LED indicationPower LED (P) green: supply
Status LED (1) red: line fault
Codingoptional mechanical coding via front socket
EU-Type Examination CertificatePTB 03 ATEX 2042
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Power consumption0.65 W
Damaging gasEN 60068-2-42
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Internal resistor1 kandOmega;
Operating frequency0 ... 15 kHz ; in frequency + counter mode ... 40 Hz
Connectionbackplane bus
UL approvalE106378
Degree of protectionIEC 60529
CertificatePF 08 CERT 1234 X
Massapprox. 90 g
Voltage8.2 V
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Degree of protectionIP20 when mounted on backplane
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Power dissipation0.65 W
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Connectionchannel I: 1+, 2/3-; direction: 4+, 5/6-
Line fault detectioncan be switched on/off for each channel via configuration tool
Environmental testEN 60068-2-14
Rated voltage12 V DC , only in connection with the power supplies LB9***
Interfacemanufacturer-specific bus to standard com unit
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Relative humidity95 % non-condensing
Vibration resistanceEN 60068-2-6
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Occupied slots1
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Switching point/switching hysteresis1.2 ... 2.1 mA / В± 0.2 mA
Relative humidityEN 60068-2-56
Electromagnetic compatibilityNE 21
IECEx approvalBVS 09.0037X
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)