Pepperl+Fuchs LB2112AR
Digital Output with Position Feedback

Pepperl+Fuchs LB2112AR
  • 1 digital output, 2 digital inputs
  • Inputs and output Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Output with watchdog
  • Module can be exchanged under voltage
Item Number: LB2112AR
423.09
-
+
Total price: 423.09
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Power dissipation1.3 W
EAC approvalRussia: RU C-IT.MIII06.B.00129
Connectionbackplane bus
Internal resistor1 kandOmega;
CertificatePF 08 CERT 1234 X
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Connectionchannel I: 1+, 4-
UL approvalE106378
Internal resistor329 andOmega;
LED indicationLED green: supply
LED red: line fault, per channel
LED yellow: signal (status), per channel
Line fault detectioncan be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
IECEx approvalBVS 09.0037X
Relative humidityEN 60068-2-56
ATEX approvalPF 08 CERT 1234 X PTB 03 ATEX 2042
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Interfacemanufacturer-specific bus to standard com unit
Line fault detectioncan be switched on/off for each channel via configuration tool
Rated voltage12 V DC , only in connection with the power supplies LB9***
Voltage8.2 V
Open loop voltage25.3 V
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Number of channels1
Minimum pulse duration1 ms
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
EU-Type Examination CertificatePTB 03 ATEX 2042
Power consumption1.8 W
Current limit53 mA
Response time20 ms (depending on bus cycle time)
Damaging gasEN 60068-2-42
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Electromagnetic compatibilityNE 21
Shock resistanceEN 60068-2-27
Connectionchannel I: 2+, 5-; channel II: 3+, 6-
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Massapprox. 110 g
Number of channels2
Occupied slots1
Codingoptional mechanical coding via front socket
Connectionbackplane bus
Environmental testEN 60068-2-14
Degree of protectionIEC 60529
Vibration resistanceEN 60068-2-6
Switching point/switching hysteresis1.2 ... 2.1 mA / В± 0.2 mA
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Degree of protectionIP20 when mounted on backplane
Relative humidity95 % non-condensing