Pepperl+Fuchs LB3005A2
HART Transmitter Power Supply, Input Isolator

Pepperl+Fuchs LB3005A2
  • 4-channel
  • Power supply for 2-wire transmitters with 4 mA ... 20 mA
  • Installation in Zone 2 or safe area
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Module can be exchanged under voltage
Item Number: LB3005A2
1041.41
-
+
Total price: 1041.41
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

4-wire transmitter (powered externally):Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-3-wire transmitter:Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-

ATEX approvalBVS 12 ATEX E 105 X
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Power consumption2.7 WConversion timemax. 100 msMassapprox. 150 gConnection2-wire transmitter (HART):Refresh time100 msRated voltage12 V DC , only in connection with the power supplies LB9***Transmitter supply voltagemin. 15 V at 20 mA ; 21.5 V at 4 mAConnectionbackplane busPower dissipation1.5 WOccupied slots2Relative humidity95 % non-condensingConnectionbackplane busHART secondary variablenoInput resistance15 andOmega;Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18Vibration resistanceEN 60068-2-6:2008Codingoptional mechanical coding via front socketDamaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3Environmental testEN 60068-2-14:2009IECEx approvalBVS 12.0055XRelative humidityEN 60068-2-78:2001Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration toolDegree of protectionIP20 when mounted on backplaneConnectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Resolution12 Bit (0 ... 26 mA)Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)Shock resistanceEN 60068-2-27:2009Number of channels4LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F) , 70 В°C (non-Ex)CertificateBVS 12 ATEX E 105 XDegree of protectionIEC 60529:2000Interfacemanufacturer-specific bus to standard com unitSupplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
HART communicationyesDamaging gasEN 60068-2-42:2003Electromagnetic compatibilityNE 21:2007