Pepperl+Fuchs LB3006A
HART Transmitter Power Supply
We ship to United States of America!
- 4-channel
- Power supply for 2-wire transmitters with 4 mA ... 20 mA
- Installation in Zone 2 or safe area
- Supply circuit 21.5 V (4 mA)
- HART communication via field bus or service bus
- Simulation mode for service operations (forcing)
- Line fault detection (LFD): one LED per channel
- Permanently self-monitoring
- Module can be exchanged under voltage
Item Number:
LB3006A
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Electromagnetic compatibilityNE 21:2007
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Shock resistance | EN 60068-2-27:2009 |
ATEX approval | BVS 12 ATEX E 115 X |
Relative humidity | 95 % non-condensing |
Damaging gas | EN 60068-2-42:2003 |
Connection | backplane bus |
Relative humidity | EN 60068-2-78:2001 |
Transmitter supply voltage | min. 15 V at 20 mA ; 21.5 V at 4 mA |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) , 70 ?°C (non-Ex) |
Power consumption | 2.7 W |
Mass | approx. 90 g |
Occupied slots | 1 |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
Connection | 2-wire transmitter (HART): supply circuit: channel I 1+, 2-, channel II 3+, 4-, channel III 5+, 6-, channel IV 7+, 8- |
Input resistance | 15 andOmega; |
Degree of protection | IEC 60529:2000 |
IECEx approval | BVS 11.0068X |
LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
Storage temperature | -25 ... 85 ?°C (-13 ... 185 ?°F) |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?± 1 mm/0.7 g; 90 minutes at each resonance |
Number of channels | 4 |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Connection | backplane bus |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
Certificate | BVS 12 ATEX E 115 X |
Coding | optional mechanical coding via front socket |
Resolution | 12 Bit (0 ... 26 mA) |
Environmental test | EN 60068-2-14:2009 |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
Vibration resistance | EN 60068-2-6:2008 |
Power dissipation | 1.5 W |
Conversion time | max. 100 ms |
HART communication | yes |
Interface | manufacturer-specific bus to standard com unit |
Refresh time | 100 ms |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
HART secondary variable | no |
Degree of protection | IP20 when mounted on backplane |