Pepperl+Fuchs LB5104A
RTD Converter

Pepperl+Fuchs LB5104A
  • 4 channels
  • Inputs Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Converter for 2-, 3- and 4-wire RTDs (Pt100 ... Pt1000), slide wire sensors etc.
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Module can be exchanged under voltage
Item Number: LB5104A
662.00
-
+
Total price: 662.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
EU-Type Examination CertificatePTB 03 ATEX 2042
Lead resistancemax. 50 andOmega; per strand
Relative humidity95 % non-condensing
Line fault detectioncan be switched on/off for each channel via configuration tool
UL approvalE106378
Linearity error0.1 %
Connectionbackplane bus
Measurement rangePt100 (18-390 andOmega;) (500 andOmega; incl. line resistance)
Pt200 (37-780 andOmega;)
Pt500 (92-1952 andOmega;)
Pt1000 (185-3905 andOmega;)
Ni100 (69-270 andOmega;)
Ni500 (345-1350 andOmega;)
Ni1000 (690-2700 andOmega;)
Degree of protectionIP20 when mounted on backplane
Rated voltage12 V DC , only in connection with the power supplies LB9***
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Environmental testEN 60068-2-14
IECEx approvalBVS 09.0037X
Connectionchannel I: resistance/potentiometer input 1 ... 4
channel II: resistance/potentiometer input 5 ... 8
channel III: resistance/potentiometer input 9 ... 12
channel IV: resistance/potentiometer input 13 ... 16
Busy after download5 ... 15 s
Connectionbackplane bus
LED indicationPower LED (P) green: supply
Status LED (I) red: line fault (collective alarm) , red flashing: communication error
Power dissipation0.35 W
Massapprox. 150 g
Slide-wire sensor0 ... 10 kandOmega;
Interfacemanufacturer-specific bus to standard com unit
Damaging gasEN 60068-2-42
Number of channels4
CertificatePF 08 CERT 1234 X
Vibration resistanceEN 60068-2-6
Electromagnetic compatibilityNE 21
Shock resistanceEN 60068-2-27
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Codingoptional mechanical coding via front socket
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
ATEX approvalPTB 03 ATEX 2042
Occupied slots2
Smallest span50 andOmega; for 0.1 % accuracy
Relative humidityEN 60068-2-56
Power consumption0.35 W
Degree of protectionIEC 60529
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Measuring current200 andmicro;A
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Conversion timemax. 500 ms (4 channels)
max. 1 s (for 4x 3-wire Pt100)
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18

Comments

No comments yet

Write a comment