Pepperl+Fuchs LB6006A
Relay output

Pepperl+Fuchs LB6006A
  • 8-channel
  • Contact 30 V AC/DC, 1 A, 30 W, 30 VA (resistive load)
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Module can be exchanged under voltage
Item Number: LB6006A
877.76
-
+
Total price: 877.76
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Shock resistanceEN 60068-2-27
Relative humidityEN 60068-2-56
Power dissipation1.4 W
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Environmental testEN 60068-2-14
Electromagnetic compatibilityNE 21
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F) , 70 В°C (non-Ex)
Codingoptional mechanical coding via front socket
Response time20 ms (depending on bus cycle time)
LED indicationPower LED (P) green: supply
Status LED (I) red: communication error
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Relative humidity95 % non-condensing
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Power consumption1.4 W
Rated voltage12 V DC , only in connection with the power supplies LB9***
UL approvalE106378
Damaging gasEN 60068-2-42
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Vibration resistanceEN 60068-2-6
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 160 g
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Number of channels8
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
IECEx approvalBVS 09.0037X
Degree of protectionIEC 60529
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Occupied slots2
CertificatePF 08 CERT 1234 X
Degree of protectionIP20 when mounted on backplane
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Connectionbackplane bus
Connectionchannel I: 1-2 NO; channel II: 3-4 NO; channel III: 5-6 NO; channel IV: 7-8 NO; channel V: 9-10 NO; channel VI: 11-12 NO; channel VII: 13-14 NO; channel VIII: 15-16 NO