Pepperl+Fuchs LB6008A
Digital Output with Shutdown Input

Pepperl+Fuchs LB6008A
  • 8-channel
  • Galvanic group isolation
  • Installation in Zone 2 or safe area
  • Module can be exchanged under voltage
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown
Item Number: LB6008A
997.65
-
+
Total price: 997.65
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
EAC approvalRussia: RU C-IT.MIII06.B.00129
Interfacemanufacturer-specific bus to standard com unit
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Degree of protectionIP20 when mounted on backplane
Connectionchannel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16-
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Connectionbackplane bus
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Connectionbackplane bus
Codingoptional mechanical coding via front socket
Environmental testEN 60068-2-14
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Massapprox. 160 g
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Response time20 ms (depending on bus cycle time)
Open loop voltage20 V
ATEX approvalPF 08 CERT 1234 X
Electromagnetic compatibilityNE 21
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Relative humidity95 % non-condensing
Vibration resistanceEN 60068-2-6
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F) , 70 В°C (non-Ex)
Occupied slots2
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Number of channels8
Damaging gasEN 60068-2-42
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
CertificatePF 08 CERT 1234 X
Power consumption2.35 W
Safety Integrity Level (SIL)SIL 2
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Power dissipation2.35 W
LED indicationLED green: supply
LED red: line fault , red flashing: communication error
IECEx approvalBVS 09.0037X
Current limit8 mA
Line fault detectioncan be switched on/off for each channel via configuration tool
Rated voltage12 V DC , only in connection with the power supplies LB9***
Relative humidityEN 60068-2-56