Pepperl+Fuchs LB6108A
Digital Output with Shutdown Input

Pepperl+Fuchs LB6108A
  • 8-channel
  • Outputs Ex ib
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Module can be exchanged under voltage
  • Galvanic group isolation
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown
Item Number: LB6108A
1024.06
-
+
Total price: 1024.06
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Environmental testEN 60068-2-14

Open loop voltage20 V
Relative humidity95 % non-condensing
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protectionIEC 60529
Electromagnetic compatibilityNE 21
Interfacemanufacturer-specific bus to standard com unit
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Vibration resistanceEN 60068-2-6
Rated voltage12 V DC , only in connection with the power supplies LB9***
CertificatePF 08 CERT 1234 X
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Number of channels8
Connectionchannel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16-
EU-Type Examination CertificatePTB 03 ATEX 2042
EAC approvalRussia: RU C-IT.MIII06.B.00129
Codingoptional mechanical coding via front socket
Relative humidityEN 60068-2-56
Response time20 ms (depending on bus cycle time)
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Connectionbackplane bus
Degree of protectionIP20 when mounted on backplane
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Power consumption2.35 W
ATEX approvalPF 08 CERT 1234 X PTB 03 ATEX 2042
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power dissipation2.35 W
Damaging gasEN 60068-2-42
Shock resistanceEN 60068-2-27
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Line fault detectioncan be switched on/off for each channel via configuration tool
LED indicationLED green: supply
LED red: line fault , communication error red flashing
Current limit8 mA
Massapprox. 160 g
IECEx approvalBVS 09.0037X
Occupied slots2
Connectionbackplane bus

Comments

No comments yet