Pepperl+Fuchs LB6110AR
Digital Output

Pepperl+Fuchs LB6110AR
We ship to United States of America!
  • 4-channel
  • Outputs Ex ia
  • Installation in Zone 2 or safe area
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
Item Number: LB6110AR
Price on Request
-
+
Total price: € 0.00
Contact our experts
  • Overview +
  • Comments +
Damaging gasEN 60068-2-42
Vibration resistanceEN 60068-2-6
Reaction time10 s
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?Β± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?Β± 1 mm/0.7 g; 90 minutes at each resonance
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Rated voltage12 V DC , only in connection with the power supplies LB9***
Massapprox. 150 g
CertificatePF 08 CERT 1234 X
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
LED indicationPower LED (P) green: supply
Status LED (I) red: line fault , red flashing: communication error
Response time10 ms (depending on bus cycle time)
Shock resistanceEN 60068-2-27
Current limit37 mA
Codingoptional mechanical coding via front socket
IECEx approvalBVS 09.0037X
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
ATEX approvalPTB 03 ATEX 2042 X
Power consumption0.15 W
Input voltage range18.5 ... 32 V DC (SELV/PELV) booster voltage
Electromagnetic compatibilityNE 21
Connectionbackplane bus / booster terminals
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Relative humidityEN 60068-2-56
Occupied slots2
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Line fault detectioncan be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Relative humidity95 % non-condensing
Open loop voltage24.5 V
Power dissipation3 W
Ambient temperature-20 ... 60 ?Β°C (-4 ... 140 ?Β°F)
Number of channels4
Connectionchannel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
EU-type examination certificatePTB 03 ATEX 2042 X
Storage temperature-25 ... 85 ?Β°C (-13 ... 185 ?Β°F)
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Internal resistormax. 370 Ω

Buy Pepperl+Fuchs LB6110AR with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a global leader in industrial automation supply. Our extensive catalog includes top brands, with worldwide delivery and competitive pricing. We focus on customer satisfaction and reliability. Experience our exceptional service and support for all your automation needs.

Comments

No comments yet

Write a comment