Pepperl+Fuchs LB8106*
EasyCom Com Unit for PROFIBUS DP/DP-V1
We ship to United States of America!
- Interface between the I/O modules and the PCS/PLC
- Com unit for 80 analog or 184 digital channels
- Communication via PROFIBUS DP
- Mounting in Zone 2, Class I/Div.2 or in the safe area
- HART communication via PROFIBUS DP V1 or service bus
- Configuration via GSD parameters from the control system
- Non-volatile memory for configuration and parameter settings
- Self configuration in redundant systems
- Permanently self-monitoring
- Outputs drive to safe state in case of failures
- Module can be exchanged under voltage
Item Number:
LB8106*
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Connection | via backplane |
Rated voltage | 5 V DC , only in connection with the power supplies LB9*** |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
Redundancy | via backplane |
PROFIBUS address | 0 ... 126 (factory standard setting: 126) |
Addressing | via configuration software |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ?± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ?± 1 mm/0.7 g; 90 minutes at each resonance |
Power consumption | 2 W |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Supported I/O modules | all LB remote I/O modules |
LED indicator | LED 1 (power supply): On = operating, fast flash = cold start LED 2 (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 3 (status process bus): flashing = PROFIBUS receive channel active LED 4 (status service bus): flashing = service bus receive channel active LED 5 (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation LED 6 (status process bus): flashing = PROFIBUS response channel active LED 7 (status servicebus): flashing = service bus response channel active |
Degree of protection | IP20 (module) , mounted on backplane |
GSE file | CGV61711.gsd/gse |
Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) |
Certificate | PF 08 CERT 1234 X |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
IECEx approval | BVS 09.0037X |
UL approval | E106378 |
Connection | backplane bus |
ATEX approval | PF 08 CERT 1234 X |
Storage temperature | -25 ... 85 ?°C (-13 ... 185 ?°F) |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Electromagnetic compatibility | NE 21 |
Mass | approx. 120 g |
Degree of protection | IEC 60529 |
Number of stations per bus segment | max. 31 (RS-485 standard) |
Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) |
Number of repeaters between Master and Slave | max. 3 |
Connection | backplane bus |
Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output |
Fieldbus type | PROFIBUS DP/DP-V1 |
HART communication | via PROFIBUS or service bus |
Buy Pepperl+Fuchs LB8106* with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. is a fast-developing industrial automation supplier. You can find the largest product catalog on our website. All your orders can be shipped in one delivery. We have the best offer for you, just contact us! We provide you with quick feedback and an accurate offer. Get an offer by sending us an inquiry via e-mail or through our online request form.