Pepperl+Fuchs LB8109H0905
Unicom Com Unit for PROFIBUS DP/DP-V1

Pepperl+Fuchs LB8109H0905
  • Interface between the I/O modules and the PCS/PLC
  • Com unit for 80 analog or 184 digital channels
  • Communication via PROFIBUS DP
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • HART communication via PROFIBUS DP V1 or service bus
  • Configuration via FDT 1.2 DTM
  • Configuration in run (CiR) for any PCS
  • Non-volatile memory for configuration and parameter settings
  • Self configuration in redundant systems
  • Permanently self-monitoring
  • Outputs drive to safe state in case of failures
  • Module can be exchanged under voltage
Item Number: LB8109H0905
1294.12
-
+
Total price: 1294.12
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Damaging gasEN 60068-2-42

Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Fieldbus typePROFIBUS DP/DP-V1
Vibration resistanceEN 60068-2-6
Addressingvia configuration software
Relative humidity95 % non-condensing
Power dissipation1.8 W
HART communicationvia PROFIBUS or service bus
LED indicationLED P: (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active
LED 1: (collective alarm): On = internal fault, flashing = no PROFIBUS connection
LED 2: (status fieldbus): flashing = PROFIBUS receive channel active
LED 3: (status service bus): flashing = service bus receive channel active
LED 4: (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation
LED 5: (status fieldbus): flashing = PROFIBUS response channel active
LED 6: (status service bus): flashing = service bus response channel active
Number of stations per bus segmentmax. 31 (RS-485 standard)
EAC approvalRussia: RU C-IT.MIII06.B.00129
Relative humidityEN 60068-2-56
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Number of repeaters between Master and Slavemax. 3
Shock resistanceEN 60068-2-27
Degree of protectionIEC 60529
CertificatePF 08 CERT 1234 X
Redundancyvia backplane
Cyclic process data240 bytes input and (simultaneously) 240 bytes output
Massapprox. 120 g
GSE fileCGV61710.gsd/gse
Electromagnetic compatibilityNE 21
UL approvalE106378
PROFIBUS address0 ... 126
(factory standard setting: 126)
Number of stations per bus linemax. 125 (PROFIBUS), max. 119 (service bus)
Connectionbackplane bus
IECEx approvalBVS 09.0037X
Supported I/O modulesall LB remote I/O modules
Power consumption1.8 W
Degree of protectionIP20 (module) , mounted on backplane
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Environmental testEN 60068-2-14
Configuration (240 bytes I/O)Standard: 80 analog, 184 digital
Universal 2I2O: 48 analog, 184 digital
Universal 4I4O: 60 analog, 120 digital
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Connectionvia backplane
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Fieldbus standardIEC 61158-2
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
ATEX approvalPF 08 CERT 1234 X
Bus lengthmax. 1000 m (FOL, 1.5 MBaud),
max. 1000 m (copper cable, 187.5 kBd),
max. 200 m (copper cable, 1.5 MBd)
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Connectionbackplane bus
Rated voltage5 V DC , only in connection with the power supplies LB9***

Comments