Pepperl+Fuchs LB9006C
Power supply

Pepperl+Fuchs LB9006C
  • Power supply for 24 V
  • Permits vertical or horizontal mounting in Zone 2
  • Use three power supplies for redundancy
  • Galvanic isolation to mains
  • Supply of I/O modules and com units
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
Item Number: LB9006C
506.00
-
+
Total price: 506.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
IECEx approvalBVS 09.0037X
PowerP5V 5.4 W, P12V 25 W - P5V for Zone 2 applications
P5V 5.4 W, P12V 39 W - P5V for applications in safe area
UL approvalE106378
Input voltage range18 ... 32 V DC (SELV/PELV)
Power consumptionmax. 30 W for Zone 2 applications
max. 45 W for applications in safe area
parallel connection with other LB9006C (autom. power sharing)
I/O modules>12, depending on the type
Degree of protectionIEC 60529
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Power dissipationapprox. 15 % of power consumption
LED indicatorPower LED (P) green: OFF in case of loss of 24 V or 12 V or 5 V
Bus coupler2
CertificatePF 08 CERT 1234 X
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F) , 70 В°C (non-Ex)
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Maximum safe voltage Um60 V DC (SELV/PELV)
Inrush current1.5 A (10 ms)
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Voltage5.4 V DC +/- 5% ,
12 V DC + 4/- 2%
Massapprox. 220 g
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Degree of protectionIP20 (module) , mounted on backplane
Electromagnetic compatibilityNE 21

Comments

No comments yet

Write a comment