Pepperl+Fuchs LGC2
Level probe

Pepperl+Fuchs LGC2
  • Device for hydrostatic pressure measurement in liquids
  • High resistance to overload
  • High-precision, robust ceramic measuring cell with long-term stability
  • Simultaneous level and temperature measuring by optional integrated Pt100 resistance thermometer
  • Measuring ranges: 0 bar ... 0.1 bar to 0 bar ... 20 bar
  • Electronics comprising 4 mA ... 20 mA output signal and integrated overvoltage protection
  • KTW and NSF drinking water approval
Item Number: LGC2
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Response timelevel probe: 400 ms (T90 time), 500 ms (T99 time)
Pt100 (optional): 160 s (T90 time), 300 s (T99 time)
Reference operating conditionslevel probe and Pt100 (optional): acc. to IEC 60770, Tamb = constant in the range:
+21 ... +33 В°C (+70 ... +91 В°F)
temperature head transmitter (optional): calibration temperature 23 В°C (+73 В°F) В± 5 K
Output signallevel probe: 4 ... 20 mA, 2-wire for hydrostatic pressure measured value
Pt100 (optional): temperature-dependent resistance value
temperature head transmitter (optional): 4 ... 20 mA Analog for temperature measured value, 2-wire
Connection3 terminals in terminal box (accessory) as standard
4 terminals in terminal block (accessory), conductor cross section 0.08 ... 2.5 mm2
Optional accessoriesPt100 resistance thermometer
suspension clamp
cable mounting screw G1-1/2
cable mounting screw N1-1/2
terminal box (IP66/IP67)
additional weight
testing adapter
shortening kit for probe connection
HUT temperature head transmitter, 2-wire, 4 ... 20 mA
Resolutioncurrent output: 1 andmicro;A
Measurement rangelevel probe:
- predefined pressure measuring ranges in bar, see type code
- customer-specific measuring ranges, factory-calibrated
Pt100 (optional): temperature measurement from -10 ... 70 В°C (+14 ... +158 В°F)
Cablelevel probe and Pt100 (optional):
- commercially available instrument cable
- terminals of the terminal box: 0.08 ... 2.5 mm2
temperature head transmitter (optional):
- commercially available instrument cable
- terminals of the terminal box: 0.08 ... 2.5 mm2
- transmitter connection: max. 1.75 mm2
probe connection (extension cable):
- total outer diameter: 8.0 mm В± 0.25 mm
- level probe: 3 x 0.2 mm2 and pressure compensation tube with PTFE filter
- Pt100 (optional): 7 x 0.2 mm2 and pressure compensation tube with PTFE filter
- pressure compensation tube with PTFE filter: external diameter Г to 20 mA signal up to В±5 % residual ripple within the permitted voltage range.
temperature head transmitter (optional): Uss 5 V at U 13 V, fmax. = 1 kHz
Ambient temperaturelevel probe and Pt100 (optional):
- Г accordance IEC 60770.
- standard version В±0.2 %
- platinum version В±0.1 %
temperature head transmitter (optional): В± 0.2 K, with Pt100: max. В± 0.9 K
Reverse polarity protectionReverse voltage protection is integrated in the level probe and in the temperature head transmitter changing the polarities has no impact on operation.
Storage temperaturelevel probe and Pt100 (optional): -40 ... +80 В°C (-40 ... +176 В°F)
temperature head transmitter (optional): -40 ... +85 В°C (-40 ... +185 В°F)
Construction typedevice with rod probe
Drinking water approvalKTW certificate and NSF approval
Warm-up timelevel probe: < 6 s
Pt100 (optional): 20 m
temperature head transmitter (optional): 4 s
CertificatePF 17 CERT 1658
Input signallevel probe: change in capacitance
Pt100 (optional): change in resistance
temperature head transmitter (optional): Pt100 resistance signal, 4-wire

Comments

No comments yet

Write a comment