Pepperl+Fuchs LHC-M51
Pressure Transmitter

Pepperl+Fuchs LHC-M51
We ship to United States of America!
  • Device for absolute pressure and gauge pressure measurement in gases, steams or liquids
  • Large selection of process connections: universal use
  • Temperature range up to 130 В°C (266 В°F)
  • Pressure range up to 400 bar (6000 psi)
  • Easy commissioning without the need for an operating tool
  • Configurable by PACTware
  • Up to SIL 2 acc. to IEC 61508
Item Number: LHC-M51
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
Accuracyreference accuracy: В±0.15 % (standard), В±0.075 % (platinum)
The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and non-reproducibility acc. to IEC 60770. The data refer to the calibrated span.
Overspill protectionsee approval (ZE)
Communication4 ... 20 mA HART (standard)
PROFIBUS PA (option)
Rated voltageversions for safe area:
11.5 ... 45 V DC, 2-wire
11.5 ... 35 V DC, HART, 2-wire
9 ... 32 V DC, PROFIBUS PA
version for hazardous area see safety information (SI)
Long-term driftup to В±0.1 % of upper range limit (URL)/year
Degree of protectionIP66, NEMA 4X
IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep)
IP69K (with separate housing and FEP cable)
Process connectionthreads ISO 228: G1/2, G1, G1-1/2, G2
threads ANSI: NPT1/2, NPT1, NPT1-1/2, NPT2
hygienic process connections: Clamp, Varivent, DRD, DIN 11851, DIN 11864, NEUMO, APV, uni adapter
flanges: EN 1092-1: DN 25 ... DN 80, ANSI 16.5: 1 ... 4 inch, JIS B2220
Measured variableabsolute or relative pressure
Measurement range0.4 ... 400 bar
max. turn down: 100:1
Drinking water approvalNSF61 approval
Degree of protectionIEC 60529:2001
Marine approvalGerman Lloyd (GL)
FM approvalsee instruction manuals (SI)
Construction typesensor: silicium sensor
metall diaphragm
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
IECEx approvalsee instruction manuals (SI)
Supplementary documentationtechnical information (TI)
manuals, brief instructions (BA, KA)
instruction manuals (SI)
control drawings (ZD)
approval (ZE)
Materialmaterials in contact with process : 316L, Alloy C, rhodium>gold
housing:
- die-cast aluminum with protective powder-coating on polyester base, housing F31
- stainless steel AISI 316L (1.4404), housing F15
measuring cell seal: no, welded measuring cell
EU-Type Examination Certificatesee instruction manuals (SI)
Designationsee technical information (TI)
CSA approvalsee instruction manuals (SI)
Connectiongland M20
thread M20, G1/2, NPT1/2
device plug M12
HAN7D Harting connector, angled
valve connector acc. ISO 4400, cable 5 m
Output signal4 ... 20 mA , analog , 2-wire
4 ... 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
digital communication signal PROFIBUS PA (Profile 3.02)
Ambient temperature-40 ... 85 В°C (-40 ... 185 В°F)
with display : -20 ... 70 В°C (-4 ... 158 В°F)

Buy Pepperl+Fuchs LHC-M51 with the best possible price and delivery terms on eltra-trade.com

Discover a wide selection of industrial electrical products at eltra-trade.com. We specialize in sourcing and delivering the parts you need promptly. Our commitment to quality and competitive pricing sets us apart. Partner with us for reliable and efficient electrical supply solutions.

Comments

No comments yet

Write a comment