Pepperl+Fuchs LUC-M**
Ultrasonic Level Sensor

Pepperl+Fuchs LUC-M**
  • Quick and simple commissioning via menu-guided onsite operation with four-line display
  • Envelope curves on the on-site display for simple diagnosis
  • Linearization function (up to 32 points) for conversion of the measured value into any unit of length, volume or flow rate
  • Non-contact measurement method minimizes service requirements
  • Optional remote display and operation (up to 20 m from transmitter)
  • Integrated temperature sensor for automatic correction of the temperature dependent sound velocity
Item Number: LUC-M**
1706.34
-
+
Total price: 1706.34
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Measurement rangeLUC-M10: max. 5 m (16.4 ft) in fluids and 2 m (6.6 ft) in bulk materials
LUC-M20: max. 8 m (26.2 ft) in fluids and 3,5 m (11.5 ft) in bulk materials
LUC-M30: max. 15 m (49.2 ft) in fluids and 7 m (23 ft) in bulk materials
LUC-M40: max. 10 m (32.8 ft) in fluids and 5 m (16.4 ft) in bulk materials
Electrical connectionterminal compartment:
In the F12 housing, the terminals are located underneath the housing cover, in the T12 housing, they are under the cover of the separate terminal compartment.
cable gland: M20x1.5 (recommended cable diameter 6 ... 10 mm (0.24 ... 0.4 inch))
cable entry G1/2 or NPT1/2
PROFIBUS PA: M12 plug connector
Degree of protectionwith closed housing, tested according to
- IP68, NEMA 6P (24 h at 1.83 m under water surface)
- IP66, NEMA 4X
with open housing: IP20, NEMA 1 (also ingress protection of the display)
Type of protection II 1/2G or II 2G EEx ia IIC T6 (KEMA 05 ATEX 1111)
II 1/2G or II 2G EEx d [ia] IIC T6 (KEMA 05 ATEX 1111)
II 1/2G or II 2G EEx em [ia] IIC T6 (KEMA 05 ATEX 1111)
II 1/2D or II 2D or II 1/3D or II 3D T115В°C or T100В°C or T95В°C (KEMA 05 ATEX 1111)
II 1/2D or II 2D or II 1/3D or II 3D T115В°C or T83В°C or T84В°C or T86В°C (KEMA 05 ATEX 1112)
II 3G EEx nA II T6
Materialmaterial in contact with process:
- LUC-M10, LUC-M20: sensor PVDF, seal EPDM
- LUC-M30: sensor UP and stainless steel 1.4571/316Ti, seal EPDM, flange PP or stainless steel 1.4571/316Ti
- LUC-M40: sensor PVDF, seal Viton or EPDM, flange PP, PVDF or stainless steel 1.4535/316L
housing: aluminum, seawater resistant, chromated, powder-coated
cover:
- aluminum, for version without on-site display
- inspection glass for version with on-site display
Measuring frequency2-wire devices: max. 0.5 Hz
4-wire devices: max. 2 Hz
dependent on the type of device and the parameter settings
Supply voltage2-wire HART (standard):
- current consumption 4 ... 20 mA
- min. terminal voltage 14 V (at 4 mA), 8 V (at 20 mA)
- max. terminal voltage 36 V
4-wire HART:
- DC version: voltage 10.5 ... 32 V, max. load 600 andOmega;
- AC version: 90 ... 253 V, max. load 600 andOmega;
PROFIBUS PA: 9 ... 32 V DC
for additional information see technical information
Explosion-hazardous areaKEMA 05 ATEX 1111, KEMA 05 ATEX 1112 , for additional certificates see www.pepperl-fuchs.com
Equipment architecture4 ... 20 mA output with HART protocol
system integration via PROFIBUS PA
Current consumption2-wire devices:
- HART: 3.6 ... 22 mA
- PROFIBUS PA: max. 13 mA
Reaction timedepends on the parameter settings:
- min. 0.5 s for 4-wire devices
- min. 2 s for 2-wire devices
Reference operating conditionstemperature = 20 В°C (68 В°F)
pressure = 1013 mbarabs
humidity = 50 %
ideal reflective surface (e. g. calm, smooth fluid surface)
no interference reflections within signal beam
set application parameters:
- tank shape = flat ceiling
- medium property = liquid
- process conditions = calm surface
Output signalaccording to the instrument version:
- 4 ... 20 mA with HART protocol
- PROFIBUS PA
MassLUC-M10: approx. 2.5 kg
LUC-M20: approx. 2.6 kg
LUC-M30: approx. 3.5 kg
LUC-M40: approx. 3 kg
Installation conditionssee technical information (TI)
Maximum measured errortypical specifications for reference operating conditions (include linearity, repeatability, and hysteresis):
В± 2 mm (0.08 inch) or 0.2% of set measuring range (empty calibration)1)
1)
whichever is greater
Dimensionssee section dimensions
Measured variabledistance between the sensor membrane and the product surface
using the linearization function, the device calculate
- level in any units
- volume in any units
- flow across measuring weirs or open channels in any units
Measured value resolutionLUC-M10, LUC-M20: 1 mm (0.04 inch)
LUC-M30, LUC-M40: 2 mm (0.08 inch)
Measuring principleThe sensor of the device transmits ultrasonic pulses in the direction of the product surface. There, the ultrasonic pulses are reflected back and received by the sensor. The device measures the time between pulse transmission and reception. The instrument uses the time (and the velocity of sound) to calculate the distance between the sensor membrane and the product surface. As the device knows the empty distance from a user entry, the device calculate the level.
Power consumption2-wire: 51 ... 800 mW
4-wire AC: max. 4 VA
4-wire DC: 0.6 ... 1 W