Pepperl+Fuchs M-LB-Ex-2142
Surge Protection Barrier
We ship to United States of America!
- Surge protection barrier for 2 signal lines
- Nominal voltage 24 V DC
- Surge protection barrier for non-grounded signal lines
- Max. surge current (8/20 µ-s) 20 kA
- Connection via screw terminals
- DIN rail mountable
- Up to SIL 3 acc. to IEC 61508
- Overview +
- Comments +
Dimensions | 6.2 x 72.4 x 93 mm |
Connection | screw terminals , max. core cross section 1 x 2.5 mm2 |
Surge protective devices for low voltage | IEC 61643-21:2000+A1:2008+A2:2012 |
Degree of protection | IEC 60529:2013 |
Maximum continuous operating voltage | 30 V DC |
Rated current | 500 mA , restrictions see derating characteristics |
Designation | - insulation spacer M-LB-2800 - terminal block USLKG5 |
Leakage current | < 3 µA at 24 V and 25 ?°C (77 ?°F) , line-line |
Connection | protected area: terminals 4, 5 unprotected area: terminals 2, 3 shielding/grounding: terminal 1 (optional) |
Series resistance | ≤ 3 Ω per line |
Mass | approx. 32 g |
Voltage protection level | max. 45 V line-line for nominal discharge current In max. 1400 V line-earth for nominal discharge current In |
Relative humidity | max. 95 % , without condensation |
EU-type examination certificate | KIWA 19 ATEX 0003 X |
Impulse discharge current (10/350 µs) | 1 kA per line (2x) |
Total discharge current (8/20 µs) | 20 kA (1x) , overstressed fault mode 3 acc. to IEC 61643-21 |
Electromagnetic compatibility | EN 61326-3-1:2017 |
Degree of protection | IP20 , after mounting of the insulation spacer |
Functional safety | IEC/EN 61508:2010 |
Storage temperature | -40 ... 85 ?°C (-40 ... 185 ?°F) |
Material | Polyamide (PA) |
Nominal voltage | 24 V DC |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Impulse rating | 1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1) |
Ambient temperature | -40 ... 80 ?°C (-40 ... 176 ?°F) Observe the temperature range limited by derating, see section derating. |
Safety Integrity Level (SIL) | SIL 3 |
Topology | non-grounded |
Insertion loss | ≤ 3 dB at 0 ... 900 kHz in 100 Ω system |
Impulse reset time | < 500 ms |
Number of protected signal lines | 2 |
Nominal discharge current (8/20 µs) | 5 kA per line (10x) |
Buy Pepperl+Fuchs M-LB-Ex-2142 with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com is your reliable source for industrial electrical parts. Our extensive product range includes various automation equipment, all available for fast delivery. We guarantee quality and competitive prices. Make us your preferred partner for all your electrical supply needs.
People also buy