We ship to United States of America!
  • Protection module for 2 signal lines
  • Nominal voltage 24 V DC
  • Protection module for non-grounded signal lines
  • Max. surge current (8/20 micro-s) 20 kA
  • Uninterruptable operation (auto reset)
  • Mounting on base module, pluggable
  • Up to SIL 3 acc. to IEC 61508
Item Number: M-LB-Ex-5142
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview +
  • Comments +
Nominal discharge current (8/20 micro/s)5 kA per line (10x)
Rated surge current (8/20 micro/s)10 kA per line (1x)
Number of protected signal lines2
Dimensions6.2 x 77 x 79 mm
Total discharge current (8/20 micro/s)20 kA (1x)
Topologynon-grounded
Series resistance 0.5 andOmega; per line at 25 ?°C (77 ?°F)
Maximum continuous operating voltage30 V DC
Relative humiditymax. 95 % , without condensation
Massapprox. 20 g
Ambient temperature-40 ... 80 ?°C (-40 ... 176 ?°F)
Observe the temperature range limited by derating, see section derating.
Impulse discharge current (10/350 micro/s)1 kA per line (2x)
Impulse rating1 kV/0.5 kA (category C1)
10 kV/5 kA (category C2)
1 kA (category D1)
Impulse reset time< 500 ms
Connectionprotected area: terminals 3, 4
unprotected area: terminals 1, 2
Storage temperature-40 ... 85 ?°C (-40 ... 185 ?°F)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Voltage protection levelmax. 45 V line-line for nominal discharge current In
max. 1400 V line-earth for nominal discharge current In
EU-Type Examination CertificateBVS 17 ATEX E 069 X
Insertion loss 0.03 dB, at 0 ... 4 kHz, in 600 andOmega;-System
3 dB, at 0 ... 600 kHz, in 100 andOmega;-System
Degree of protectionIEC 60529:2013
Safety Integrity Level (SIL)SIL 3
Designationsystem components:
- base module with screw terminals M-LB-Ex-5000
- base module with spring terminals M-LB-Ex-5000.SP
- place holder module M-LB-Ex-5900
- separation wall M-UPR-I
Mountingpluggable in base module for mounting on 35 mm DIN mounting rail
Rated current500 mA , restrictions see derating characteristics
Functional safetyIEC/EN 61508:2010
Leakage current< 3 andmicro;A at 24 V and 25 ?°C (77 ?°F) , line-line
Surge protective devices for low voltageEN 61643-21:2001+A1:2009+A2:2013
IEC 61643-21:2001+A1:2008+A2:2012
Nominal voltage24 V DC
Degree of protectionIP20