Pepperl+Fuchs NCB8-18GM40-N0-OG
Inductive sensor
We ship to United States of America!
Series: Cylindrical type, Housing diameter: 18 mm, Housing material: Stainless steel 1.4305 / AISI 303, Rated operating distance: 8 mm, Connection type: cable PUR (halogen-free) , 2 m blue , Oil resistant , Flame-retardant as per IEC 60332-1, Output type: 2-wire, Installation: flush, Type of voltage: DC, ATEX 3G
Item Number:
NCB8-18GM40-N0-OG
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
General specifications | ||
Switching element function | NAMUR, NC | |
Rated operating distance | 8 mm | |
Installation | flush | |
Output polarity | NAMUR | |
Assured operating distance | 0 ... 6.48 mm | |
Reduction factor rAl | 0.39 | |
Reduction factor rCu | 0.36 | |
Reduction factor r304 | 0.71 | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 kOm) | |
Switching frequency | 0 ... 1500 Hz | |
Hysteresis | 1 ... 15 typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | yes | |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
Current consumption | ||
Measuring plate not detected | min. 2.2 mA | |
Measuring plate detected | less than or equal to 1 mA | |
Switching state indicator | all direction LED, yellow | |
Functional safety related parameters | ||
MTTFd | 2660 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Electromagnetic compatibility | NE 21:2007 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated less than or equal to 36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 80 °C (-13 ... 176 °F) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Connection type | cable PUR (halogen-free) , 2 m blue , Oil resistant , Flame-retardant as per IEC 60332-1 | |
Core cross-section | 2x 1 mm2 , black | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Housing diameter | 18 mm | |
Degree of protection | IP66 / IP67 | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G- 2G- 3G |
Buy Pepperl+Fuchs NCB8-18GM40-N0-OG with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com is an online store of industrial automation equipment. New items of automation products are added every day. Your order can be quickly delivered throughout Europe and around the world. We offer you good value for money. We provide our customers with a very quick response and good conditions. Using our professional services will help you be more competitive in the market and it will save you time.