Item Number: NCN3-F25F-N4-Y47292
- For installation in housing
- Direct mounting on standard actuators
- ATEX & IECEX certifications
- Overview
- Datasheet
- Alternative numbers
- Comments
Rated operating distance | 3 mm |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 15 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW : 95 В°C (203 В°F) |
Effective internal inductance | max. 100 µH The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Mass | 217 g |
Hysteresis | typ. 5 % |
Effective internal capacitance | max. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Reduction factor rSt37 | 1 |
Sensing face | PBT |
UL approval | cULus Listed, General Purpose |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Switching state indicator | LED, yellow |
Switching function | 2 x normally closed (NC) |
Effective internal capacitance | max. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
CE marking | [*PD-Z02585A*] |
Effective internal capacitance | max. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Core cross-section | 4 x 0.34 mm2 |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 15 V , Ii = 25 mA , Pi = 34 mW , T6 : 75 В°C (167 В°F) T5 : 90 В°C (194 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW , T6 : 70 В°C (158 В°F) T5 : 85 В°C (185 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW , T6 : 60 В°C (140 В°F) T5 : 75 В°C (167 В°F) T4 : 95 В°C (203 В°F) T3 : 95 В°C (203 В°F) T2 : 95 В°C (203 В°F) T1 : 95 В°C (203 В°F) |
Switching frequency | 0 ... 1500 Hz |
Equipment protection level | Ga , Gb , Gc (ic) , Da , Mb |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. |
Type of protection | intrinsic safety |
Connection type | cable PVC , 5 m |
Reduction factor rAl | 0.52 |
Short-circuit protection | yes |
Output type | NAMUR |
Effective internal capacitance | max. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 75 В°C (167 В°F) T5 : 90 В°C (194 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 70 В°C (158 В°F) T5 : 85 В°C (185 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 60 В°C (140 В°F) T5 : 75 В°C (167 В°F) T4 : 95 В°C (203 В°F) T3 : 95 В°C (203 В°F) T2 : 95 В°C (203 В°F) T1 : 95 В°C (203 В°F) |
Tightening torque, fastening screws | M5 x 25 : 2.7 Nm |
CE marking | [*PD-Z02585A*] |
Housing material | PBT |
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
MTTFd | 1010 a |
Assured operating distance | 0 ... 2.43 mm |
Degree of protection | IP67 |
Type of protection | intrinsic safety |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 15 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW : 95 В°C (203 В°F) |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
Output type | 2-wire |
Type of protection | intrinsic safety |
Effective internal inductance | max. 100 µH The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Reduction factor r304 | 0.86 |
Installation | flush mountable |
Reduction factor rBrass | 0.54 |
Effective internal capacitance | max. 100 nF A cable length of 10 m is considered. |
CE marking | [*PD-Z02585A*] |
Storage temperature | -40 ... 100 В°C (-40 ... 212 В°F) |
Actual operating distance | 2.7 ... 3.3 mm typ. |
Use in the hazardous area | see instruction manuals |
Effective internal inductance | max. 100 µH The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Type of protection | intrinsic safety |
Reverse polarity protection | reverse polarity protected |
Mission Time (TM) | 20 a |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
CSA approval | cCSAus Listed, General Purpose |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 100 µH The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Diagnostic Coverage (DC) | 0 % |
CE marking | [*PD-Z02585A*] |
Time delay before availability | ≤ 1 ms |
Reduction factor rCu | 0.43 |
Type of protection | intrinsic safety |