Pepperl+Fuchs NCN3-F31K2-N4-B13-S
Inductive sensor

Pepperl+Fuchs NCN3-F31K2-N4-B13-S
  • Direct mounting on standard actuators
  • ATEX IECEX certifications
  • Usable up to SIL 2 acc. to IEC 61508
  • Weatherproof housing for outdoor applications
  • LEDs for switching state of sensor and solenoid valve
  • Plug-in terminals
  • Temperature range
    -40 ... 100 В°C (-40 ... 212 В°F)
Item Number: NCN3-F31K2-N4-B13-S
271.82
-
+
Total price: 271.82
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Switching state indicatorLED, yellow
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 70 В°C (158 В°F)
T5 : 85 В°C (185 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 70 В°C (158 В°F)
T5 : 85 В°C (185 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 60 В°C (140 В°F)
T5 : 75 В°C (167 В°F)
T4 : 75 В°C (167 В°F)
T3 : 75 В°C (167 В°F)
T2 : 75 В°C (167 В°F)
T1 : 75 В°C (167 В°F)
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 15 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 52 mA , Pi = 169 mW : 75 В°C (167 В°F)
Switching function2 x normally closed (NC)
Time delay before availability 1 ms
UL approvalcULus Listed, General Purpose, Class 2 Power Source
Effective internal inductancemax. 100 andmicro;H
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Reverse polarity protectionyes, with reversed output LED is out of function, therfore more power for solenoid valve
Connection (system side)Screw terminals, tightening torque min. 0.5 Nm
Stripped length 7 mm , M20 x 1.5
Hysteresistyp. 5 %
Currentmax. 240 mA
Rated operating distance3 mm
Type of protectionintrinsic safety
Effective internal inductancemax. 100 andmicro;H
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Effective internal inductancemax. 100 andmicro;H
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
negligibly small
Use in the hazardous areasee instruction manuals
Degree of protectionIP66 / IP68 / IP69
Storage temperature-40 ... 100 В°C (-40 ... 212 В°F)
Reduction factor rBrass 0.5
Diagnostic Coverage (DC)0 %
Equipment protection levelGa , Gb , Gc (ic) , Mb
Short-circuit protectionno
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 15 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 70 В°C (158 В°F)
T5 : 85 В°C (185 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 70 В°C (158 В°F)
T5 : 85 В°C (185 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 15 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 60 В°C (140 В°F)
T5 : 75 В°C (167 В°F)
T4 : 75 В°C (167 В°F)
T3 : 75 В°C (167 В°F)
T2 : 75 В°C (167 В°F)
T1 : 75 В°C (167 В°F)
MTTFd1730 a
CE marking[*PD-Z02585A*]
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Reduction factor r304 0.7
Type of protectionintrinsic safety
Output type2-wire
Reduction factor rCu 0.4
Actual operating distance2.7 ... 3.3 mm typ.
Connection (valve side)like connection (system side)
Output typeNAMUR
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
CE marking[*PD-Z02586A*]
CCC approvalCCC approval / marking not required for products rated 36 V
Type of protectionintrinsic safety
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
CE marking[*PD-Z02585A*]
Core cross-section (valve side)like core cross section (system side)
NoteLED switch-off
Mission Time (TM)20 a
Voltagemax. 32 V DC
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Tightening torque, cable glandM20 x 1.5 ; max. 4 Nm
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Short-circuit protectionyes
Housing basePC
Tightening torque, housing screws 2 Nm
Effective internal capacitancemax. 100 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Valve status indicatorLED, yellow
Effective internal inductancemax. 100 andmicro;H
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Core cross-section (system side)rigid: 0.14 ... 2.5 mm2
flexible: 0.14 ... 1.5 mm2
flexible with core-end sleeve: 0.25 ... 1.5 mm2
Installationflush mountable
Reverse polarity protectionreverse polarity protected
CE marking[*PD-Z02585A*]
Assured operating distance0 ... 2.4 mm
For assured operating distance sar see Manual Functional Safety.
Housing materialrugged, translucent polycarbonate (PC) optimised for outdoor use
Type of protectionintrinsic safety
Tightening torque, stopping plug1 Nm
Switching frequency0 ... 3 kHz
Reduction factor rSt37 1
Nominal voltage8 V
Maximum values of the valve circuitThe value applies to each valve circuit.
A cable length of 10 m is considered.
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Ambient temperature-40 ... 100 В°C (-40 ... 212 В°F)
Actuating elementStainless steel 1.4305 / AISI 303
8.5 mm x 8.5 mm x 0.5 mm
Reduction factor rAl 0.4
Safety Integrity Level (SIL)SIL 2

Comments

No comments yet