Pepperl+Fuchs NJ10-30GK-SN-40M
Inductive sensor

Pepperl+Fuchs NJ10-30GK-SN-40M
  • 10 mm flush
  • Usable up to SIL 3 acc. to IEC 61508
  • ATEX approval Ex-i and Ex-nA/tc for zone 0-2 and zone 20-22
  • Degree of protection IP68
Item Number: NJ10-30GK-SN-40M
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
EAC conformityTR CU 012/2011
Possible characteristicsmaximum operating voltage UBmax , load current IL , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Safety Integrity Level (SIL)up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the ""exida Functional Safety Assessment"" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
Effective internal inductancemax. 150 andmicro;H
A cable length of 10 m is considered.
NoteSecurity relevant only up to -40В°C
CE marking[*PD-Z02585A*]
Core cross-section0.75 mm2
Housing materialCrastin (PBTB), black
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Type of protectionintrinsic safety
CE marking[*PD-Z02586A*]
Nominal voltage8.2 V
CCC approvalCCC approval / marking not required for products rated 36 V
Output typeNAMUR with safety function
Rated operating distance10 mm
Use in the hazardous areasee instruction manuals
Switching frequency0 ... 300 Hz
Type of protection""n""
Degree of protectionIP68
UL approvalcULus Listed, General Purpose
CE marking[*PD-Z02585A*]
Possible characteristicsmaximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax
Type of protectionintrinsic safety
MTTFd11850 a
Switching functionNormally closed (NC)
Connection typecable silicone , 40 m
Reduction factor r304 0.85
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Safety Integrity Level (SIL)SIL 3
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F)
Effective internal inductancemax. 150 andmicro;H
A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
using an amplifier in accordance with EN 60947-5-6 : 58 В°C (136.4 В°F)
at UBmax = 9 V , RV = 562 andOmega; : 58 В°C (136.4 В°F)
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
using an amplifier in accordance with EN 60947-5-6 : 58 В°C (136.4 В°F)
at UBmax = 9 V , RV = 562 andOmega; : 58 В°C (136.4 В°F)
Mission Time (TM)20 a
Ambient temperature-50 ... 100 В°C (-58 ... 212 В°F)
Sensing faceCrastin (PBTB), black
Type of protectionProtection by enclosure ""tc""
Reduction factor rCu 0.3
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 В°C (163.4 В°F)
T5 : 88 В°C (190.4 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 69 В°C (156.2 В°F)
T5 : 84 В°C (183.2 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 51 В°C (123.8 В°F)
T5 : 66 В°C (150.8 В°F)
T4 : 80 В°C (176 В°F)
T3 : 80 В°C (176 В°F)
T2 : 80 В°C (176 В°F)
T1 : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 39 В°C (102.2 В°F)
T5 : 54 В°C (129.2 В°F)
T4 : 61 В°C (141.8 В°F)
T3 : 61 В°C (141.8 В°F)
T2 : 61 В°C (141.8 В°F)
T1 : 61 В°C (141.8 В°F)
Equipment protection levelGa , Gb , Gc (nA) , Da , Dc , Mb
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F)
CE marking[*PD-Z02586A*]
Effective internal inductancemax. 150 andmicro;H
A cable length of 10 m is considered.
Installationflush
Diagnostic Coverage (DC)0 %
Output type2-wire
Type of protectionintrinsic safety
Reduction factor rAl 0.4
Assured operating distance0 ... 8.1 mm
Effective internal inductancemax. 150 andmicro;H
A cable length of 10 m is considered.
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.

Comments

No comments yet

Write a comment