Pepperl+Fuchs NJ15-30GK-N-150-Y38977
Inductive sensor
- Temperature range
-25 ... 150 В°C (-13 ... 302 В°F)
- Overview
- Comments
This product is not available!
Reduction factor rCu0.3
Reduction factor r304 | 0.85 |
Switching function | Normally closed (NC) |
Core cross-section | 0.38 mm2 |
Rated operating distance | 15 mm |
MTTFd | 4540 a |
Degree of protection | IP65 |
Switching frequency | 0 ... 100 Hz |
Appropriate type | NJ15-30GK-N-150... |
ATEX marking | II 1D Ex ia IIIC T135В°C Da The Ex-related marking can also be printed on the enclosed label. |
Diagnostic Coverage (DC) | 0 % |
Appropriate type | NJ15-30GK-N-150... |
Connection type | cable PTFE , 10 m |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
CE marking | [*PD-Z02585A*] |
Output type | 2-wire |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Mission Time (TM) | 20 a |
Sensing face | PPS |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Effective internal capacitance | max. 140 nF ; a cable length of 10 m is considered. |
Use in the hazardous area | see instruction manuals |
Output type | NAMUR |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
Assured operating distance | 0 ... 12.15 mm |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Housing material | PPS |
Installation | non-flush |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Ambient temperature | -25 ... 150 В°C (-13 ... 302 В°F) |
Effective internal capacitance | max. 140 µF A cable length of 10 m is considered. |
Nominal voltage | 8 V |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
CE marking | [*PD-Z02585A*] |
CSA approval | cCSAus Listed, General Purpose |
Appropriate type | NJ15-30GK-N-150... |
Reduction factor rAl | 0.4 |
Effective internal capacitance | max. 140 nF ; a cable length of 10 m is considered. |
People also buy
Comments