Pepperl+Fuchs NJ15-30GK-N-150-Y38977
Inductive sensor
We ship to United States of America!
- Temperature range
-25 ... 150 В°C (-13 ... 302 В°F)
Item Number:
NJ15-30GK-N-150-Y38977
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
This product is not available!
Reduction factor rCu0.3
Reduction factor r304 | 0.85 |
Switching function | Normally closed (NC) |
Core cross-section | 0.38 mm2 |
Rated operating distance | 15 mm |
MTTFd | 4540 a |
Degree of protection | IP65 |
Switching frequency | 0 ... 100 Hz |
Appropriate type | NJ15-30GK-N-150... |
ATEX marking | II 1D Ex ia IIIC T135В°C Da The Ex-related marking can also be printed on the enclosed label. |
Diagnostic Coverage (DC) | 0 % |
Appropriate type | NJ15-30GK-N-150... |
Connection type | cable PTFE , 10 m |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
CE marking | [*PD-Z02585A*] |
Output type | 2-wire |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 100 µH A cable length of 10 m is considered. |
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Mission Time (TM) | 20 a |
Sensing face | PPS |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Effective internal capacitance | max. 140 nF ; a cable length of 10 m is considered. |
Use in the hazardous area | see instruction manuals |
Output type | NAMUR |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
Assured operating distance | 0 ... 12.15 mm |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Housing material | PPS |
Installation | non-flush |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Ambient temperature | -25 ... 150 В°C (-13 ... 302 В°F) |
Effective internal capacitance | max. 140 µF A cable length of 10 m is considered. |
Nominal voltage | 8 V |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
CE marking | [*PD-Z02585A*] |
CSA approval | cCSAus Listed, General Purpose |
Appropriate type | NJ15-30GK-N-150... |
Reduction factor rAl | 0.4 |
Effective internal capacitance | max. 140 nF ; a cable length of 10 m is considered. |
Buy Pepperl+Fuchs NJ15-30GK-N-150-Y38977 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. offers industrial control products. Our online catalog offers a wide selection of product types and sizes. We consolidate all your goods and send them in one delivery. Become our client and get unbelievable prices for all automation equipment. Quotes are always sent quickly after your request. During the past years, we managed to develop enough to satisfy the requirements of our customers.
People also buy
Comments