Pepperl+Fuchs NJ15+U4+W-BHMS3-N.O.
Inductive sensor
Series: VariKont ®, Housing material: PBT, Rated operating distance: 15 mm, Connection type: Quick disconnect type BHMS3, Output type: 2-wire, Installation: non-flush, Type of voltage: AC
- Overview
- Comments
General specifications | ||
Switching element function | AC | |
Rated operating distance | 15 mm | |
Installation | non-flush | |
Output polarity | AC | |
Assured operating distance | 0 ... 12.15 mm | |
Reduction factor rAl | 0.35 | |
Reduction factor rCu | 0.35 | |
Reduction factor r304 | 0.8 | |
Nominal ratings | ||
Operating voltage | 20 ... 253 V 1) | |
Switching frequency | 0 ... 20 Hz | |
Hysteresis | 1 ... 10 typ. 5 % | |
Voltage drop | less than or equal to 12 V | |
Momentary current (20 ms, 0.1 Hz) | 0 ... 3000 mA | |
Operating current | 8 ... 500 mA | |
Off-state current | 0.5 ... 1.95 mA typ. 1.2 mA | |
Operating voltage indicator | LED, green | |
Switching state indicator | LED, yellow | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | Certified by China Compulsory Certification (CCC) | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Connection type | Quick disconnect type BHMS3 | |
Housing material | PBT | |
Sensing face | PBT | |
Degree of protection | IP68 | |
Note | 1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V |