Pepperl+Fuchs NJ2,5-14GM-N-V1-Y21146 Inductive sensor


Item Number: NJ2,5-14GM-N-V1-Y21146
- Comfort series
- Usable up to SIL 2 acc. to IEC 61508
- 2.5 mm flush
- Overview
- Datasheet
- Alternative numbers
- Comments
Housing material | Stainless steel 1.4305 / AISI 303 |
UL approval | cULus Listed, General Purpose |
Connection type | Connector plug M12 x 1 , 4-pin |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Effective internal inductance | max. 50 µH A cable length of 10 m is considered. |
Degree of protection | IP67 |
CE marking | [*PD-Z02585A*] |
Switching function | Normally closed (NC) |
Installation | flush |
Diagnostic Coverage (DC) | 0 % |
MTTFd | 5887 a |
Appropriate type | NJ2,5-14GM-N... |
Assured operating distance | 0 ... 2.02 mm |
Rated operating distance | 2.5 mm |
Mission Time (TM) | 20 a |
ATEX marking | The Ex-related marking can also be printed on the enclosed label. |
Switching frequency | 0 ... 1500 Hz |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
CSA approval | cCSAus Listed, General Purpose |
Use in the hazardous area | see instruction manuals |
Sensing face | PBT |
Effective internal capacitance | max. 30 µF A cable length of 10 m is considered. |
Reduction factor rCu | 0.3 |
Reduction factor rAl | 0.4 |
Effective internal capacitance | max. 30 nF ; a cable length of 10 m is considered. |
Output type | 2-wire |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Output type | NAMUR |
ATEX marking | The Ex-related marking can also be printed on the enclosed label. |
Nominal voltage | 8 V |
Reduction factor r304 | 0.85 |
Ambient temperature | 0 ... 90 В°C (32 ... 194 В°F) |
CE marking | [*PD-Z02585A*] |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Appropriate type | NJ2,5-14GM-N... |