Pepperl+Fuchs NJ2-V3-N-0,075M
Inductive sensor

Pepperl+Fuchs NJ2-V3-N-0,075M
  • 2 mm flush
  • Usable up to SIL 2 acc. to IEC 61508
Item Number: NJ2-V3-N-0,075M
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

Installationflush

Assured operating distance0 ... 1.62 mm
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Effective internal capacitancemax. 40 nF ; a cable length of 10 m is considered.
Effective internal inductancemax. 50 µH ; a cable length of 10 m is considered.
Output type2-wire
Appropriate typeNJ 2-V3-N ...
Output typeNAMUR
Hysteresis0.01 ... 0.1 mm
Appropriate typeNJ 2-V3-N ...
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
MTTFd11775 a
Diagnostic Coverage (DC)0 %
Reduction factor r3040.7
Switching functionNormally closed (NC)
Core cross-section0.14 mm2
Effective internal capacitancemax. 40 nF ; a cable length of 10 m is considered.
Switching frequency0 ... 1000 Hz
Housing materialPBT
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Effective internal inductancemax. 50 µH ; a cable length of 10 m is considered.
Degree of protectionIP67
Rated operating distance2 mm
ATEX marking II 1D Ex ia IIIC T135В°C Da
The Ex-related marking can also be printed on the enclosed label.
Effective internal capacitancemax. 40 nF ; a cable length of 10 m is considered.
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
Sensing facePBT
Connection typecable PVC , 75 mm , Wire ends, 3 mm, stripped and tin-plated
ATEX marking II 1G Ex ia IIC T6…T1 Ga
The Ex-related marking can also be printed on the enclosed label.
Reduction factor rAl0.25
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6…T1 Ga
The Ex-related marking can also be printed on the enclosed label.
Appropriate typeNJ 2-V3-N ...
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
EAC conformityTR CU 012/2011
Use in the hazardous areasee instruction manuals
CE marking[*PD-Z02585A*]
Reduction factor rCu0.2
CE marking[*PD-Z02585A*]
Effective internal inductancemax. 50 µH ; a cable length of 10 m is considered.
Ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
CCC approvalCCC approval / marking not required for products rated ≤36 V
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012
Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions
Mission Time (TM)20 a
CSA approvalcCSAus Listed, General Purpose
Nominal voltage8.2 V (Ri approx. 1 kΩ)

Comments

No comments yet