Pepperl+Fuchs NJ2-V3-N-0,075M Inductive sensor


Item Number: NJ2-V3-N-0,075M
- 2 mm flush
- Usable up to SIL 2 acc. to IEC 61508
- Overview
- Datasheet
- Alternative numbers
- Comments
Installationflush
Assured operating distance | 0 ... 1.62 mm |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Output type | 2-wire |
Appropriate type | NJ 2-V3-N ... |
Output type | NAMUR |
Hysteresis | 0.01 ... 0.1 mm |
Appropriate type | NJ 2-V3-N ... |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
MTTFd | 11775 a |
Diagnostic Coverage (DC) | 0 % |
Reduction factor r304 | 0.7 |
Switching function | Normally closed (NC) |
Core cross-section | 0.14 mm2 |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
Switching frequency | 0 ... 1000 Hz |
Housing material | PBT |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Degree of protection | IP67 |
Rated operating distance | 2 mm |
ATEX marking | The Ex-related marking can also be printed on the enclosed label. |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
Sensing face | PBT |
Connection type | cable PVC , 75 mm , Wire ends, 3 mm, stripped and tin-plated |
ATEX marking | The Ex-related marking can also be printed on the enclosed label. |
Reduction factor rAl | 0.25 |
CE marking | [*PD-Z02585A*] |
ATEX marking | The Ex-related marking can also be printed on the enclosed label. |
Appropriate type | NJ 2-V3-N ... |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
EAC conformity | TR CU 012/2011 |
Use in the hazardous area | see instruction manuals |
CE marking | [*PD-Z02585A*] |
Reduction factor rCu | 0.2 |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Mission Time (TM) | 20 a |
CSA approval | cCSAus Listed, General Purpose |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
People also buy
Comments
No comments yet