Pepperl+Fuchs NJ2-V3-N-Y220141
Inductive sensor
We ship to United States of America!
- Comfort series
Item Number:
NJ2-V3-N-Y220141
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Degree of protection | IP67 |
Rated operating distance | 2 mm |
Ambient temperature | -25 ... 100 ?°C (-13 ... 212 ?°F) |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
Use in the hazardous area | see instruction manuals |
Sensing face | PBT |
CSA approval | cCSAus Listed, General Purpose |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
CE marking | [*PD-Z02585A*] |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135?°C Da The Ex-related marking can also be printed on the enclosed label. |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Core cross-section | 0.14 mm2 |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Switching frequency | 0 ... 1000 Hz |
Reduction factor r304 | 0.7 |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Hysteresis | 0.01 ... 0.1 mm |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Appropriate type | NJ 2-V3-N ... |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Switching function | Normally closed (NC) |
Reduction factor rCu | 0.2 |
Connection type | cable PVC , 170 mm |
Output type | NAMUR |
Reduction factor rAl | 0.25 |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Effective internal capacitance | max. 40 nF ; a cable length of 10 m is considered. |
ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Appropriate type | NJ 2-V3-N ... |
Appropriate type | NJ 2-V3-N ... |
Assured operating distance | 0 ... 1.62 mm |
Housing material | PBT |
Output type | 2-wire |
Nominal voltage | 8 V |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Installation | flush |