Pepperl+Fuchs NJ4-12GM-N-Y19785 Inductive sensor


Item Number: NJ4-12GM-N-Y19785
- Comfort series
- Overview
- Datasheet
- Alternative numbers
- Comments
CE marking | [*PD-Z02585A*] |
Switching frequency | 0 ... 1500 Hz |
Effective internal capacitance | max. 45 nF ; a cable length of 10 m is considered. |
Appropriate type | NJ 4-12GM-N... |
Mission Time (TM) | 20 a |
MTTFd | 11774 a |
Connection type | cable PVC , 2 m |
Degree of protection | IP68 |
Effective internal capacitance | max. 45 nF ; a cable length of 10 m is considered. |
Output type | NAMUR |
Core cross-section | 0.34 mm2 |
Output type | 2-wire |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
CE marking | [*PD-Z02585A*] |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. |
Appropriate type | NJ 4-12GM-N... |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
CSA approval | cCSAus Listed, General Purpose |
Rated operating distance | 4 mm |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Sensing face | PBT |
Switching function | Normally closed (NC) |
ATEX marking | |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
ATEX marking | |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Appropriate type | NJ 4-12GM-N... |
ATEX marking | |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection ""Intrinsic safety"" Use is restricted to the following stated conditions |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Diagnostic Coverage (DC) | 0 % |
Ambient temperature | -25 ... 100 В°C (-13 ... 212 В°F) |
CE marking | [*PD-Z02585A*] |
Housing material | Stainless steel 1.4305 / AISI 303 |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Reduction factor rCu | 0.3 |
Use in the hazardous area | see instruction manuals |
Assured operating distance | 0 ... 3.24 mm |
Installation | non-flush |
Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
Effective internal capacitance | max. 45 nF ; a cable length of 10 m is considered. |
Reduction factor rAl | 0.4 |
Reduction factor r304 | 0.85 |
Hysteresis | 3 % |