Pepperl+Fuchs NJ8-18GK-SN-10M-Y70101418
Inductive sensor

Pepperl+Fuchs NJ8-18GK-SN-10M-Y70101418
  • 8 mm non-flush
  • ATEX approval Ex-i for zone 0-2 and zone 20-22
  • Degree of protection IP68
Item Number: NJ8-18GK-SN-10M-Y70101418
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments
CE marking[*PD-Z02585A*]
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F)
Reduction factor rAl 0.4
Type of protectionintrinsic safety
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F)
Ambient temperature-40 ... 100 В°C (-40 ... 212 В°F)
Nominal voltage8.2 V
CE marking[*PD-Z02585A*]
Effective internal inductancemax. 200 andmicro;H
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Type of protectionintrinsic safety
Equipment protection levelGa , Gb , Gc (ic) , Da , Mb
Assured operating distance0 ... 6.48 mm
Installationnon-flush
Effective internal capacitancemax. 120 nF
The value is applicable for one sensor circuit.
A cable length of 10 m is considered.
Output typeNAMUR with safety function
Core cross-section0.75 mm2
Sensing faceCrastin (PBTB), black
CE marking[*PD-Z02585A*]
Type of protectionintrinsic safety
Effective internal inductancemax. 200 andmicro;H
A cable length of 10 m is considered.
Switching frequency0 ... 200 Hz
CCC approvalCCC approval / marking not required for products rated 36 V
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 55 В°C (131 В°F)
T5 : 55 В°C (131 В°F)
T4 : 55 В°C (131 В°F)
T3 : 55 В°C (131 В°F)
T2 : 55 В°C (131 В°F)
T1 : 55 В°C (131 В°F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 55 В°C (131 В°F)
T5 : 55 В°C (131 В°F)
T4 : 55 В°C (131 В°F)
T3 : 55 В°C (131 В°F)
T2 : 55 В°C (131 В°F)
T1 : 55 В°C (131 В°F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 41 В°C (105.8 В°F)
T5 : 41 В°C (105.8 В°F)
T4 : 41 В°C (105.8 В°F)
T3 : 41 В°C (105.8 В°F)
T2 : 41 В°C (105.8 В°F)
T1 : 41 В°C (105.8 В°F)
at Ui = 20 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 29 В°C (84.2 В°F)
T5 : 29 В°C (84.2 В°F)
T4 : 29 В°C (84.2 В°F)
T3 : 29 В°C (84.2 В°F)
T2 : 29 В°C (84.2 В°F)
T1 : 29 В°C (84.2 В°F)
Mission Time (TM)20 a
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
MTTFd11850 a
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 В°C (163.4 В°F)
T5 : 88 В°C (190.4 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 69 В°C (156.2 В°F)
T5 : 84 В°C (183.2 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 51 В°C (123.8 В°F)
T5 : 66 В°C (150.8 В°F)
T4 : 80 В°C (176 В°F)
T3 : 80 В°C (176 В°F)
T2 : 80 В°C (176 В°F)
T1 : 80 В°C (176 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 39 В°C (102.2 В°F)
T5 : 54 В°C (129.2 В°F)
T4 : 61 В°C (141.8 В°F)
T3 : 61 В°C (141.8 В°F)
T2 : 61 В°C (141.8 В°F)
T1 : 61 В°C (141.8 В°F)
Housing materialCrastin (PBTB), black
Reduction factor rCu 0.3
Connection typecable silicone , 10 m
Reduction factor r304 0.85
CE marking[*PD-Z02586A*]
Effective internal inductancemax. 200 andmicro;H
A cable length of 10 m is considered.
Diagnostic Coverage (DC)0 %
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Degree of protectionIP68
Type of protectionintrinsic safety
Use in the hazardous areasee instruction manuals
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Type of protectionintrinsic safety
Rated operating distance8 mm
Effective internal capacitancemax. 120 nF
A cable length of 10 m is considered.
Output type2-wire
Switching functionNormally closed (NC)
Effective internal inductancemax. 200 andmicro;H
A cable length of 10 m is considered.
EAC conformityTR CU 012/2011
Effective internal inductancemax. 200 andmicro;H
A cable length of 10 m is considered.

Comments

No comments yet

Write a comment