Pepperl+Fuchs NJ8-18GK-SN-10M-Y70101418
Inductive sensor
We ship to United States of America!
- 8 mm non-flush
- ATEX approval Ex-i for zone 0-2 and zone 20-22
- Degree of protection IP68
Item Number:
NJ8-18GK-SN-10M-Y70101418
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
CE marking | [*PD-Z02585A*] |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F) |
Reduction factor rAl | 0.4 |
Type of protection | intrinsic safety |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F) |
Ambient temperature | -40 ... 100 В°C (-40 ... 212 В°F) |
Nominal voltage | 8.2 V |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 200 andmicro;H The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Type of protection | intrinsic safety |
Equipment protection level | Ga , Gb , Gc (ic) , Da , Mb |
Assured operating distance | 0 ... 6.48 mm |
Installation | non-flush |
Effective internal capacitance | max. 120 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered. |
Output type | NAMUR with safety function |
Core cross-section | 0.75 mm2 |
Sensing face | Crastin (PBTB), black |
CE marking | [*PD-Z02585A*] |
Type of protection | intrinsic safety |
Effective internal inductance | max. 200 andmicro;H A cable length of 10 m is considered. |
Switching frequency | 0 ... 200 Hz |
CCC approval | CCC approval / marking not required for products rated 36 V |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 55 В°C (131 В°F) T5 : 55 В°C (131 В°F) T4 : 55 В°C (131 В°F) T3 : 55 В°C (131 В°F) T2 : 55 В°C (131 В°F) T1 : 55 В°C (131 В°F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 55 В°C (131 В°F) T5 : 55 В°C (131 В°F) T4 : 55 В°C (131 В°F) T3 : 55 В°C (131 В°F) T2 : 55 В°C (131 В°F) T1 : 55 В°C (131 В°F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 41 В°C (105.8 В°F) T5 : 41 В°C (105.8 В°F) T4 : 41 В°C (105.8 В°F) T3 : 41 В°C (105.8 В°F) T2 : 41 В°C (105.8 В°F) T1 : 41 В°C (105.8 В°F) at Ui = 20 V , Ii = 76 mA , Pi = 242 mW , T6 : 29 В°C (84.2 В°F) T5 : 29 В°C (84.2 В°F) T4 : 29 В°C (84.2 В°F) T3 : 29 В°C (84.2 В°F) T2 : 29 В°C (84.2 В°F) T1 : 29 В°C (84.2 В°F) |
Mission Time (TM) | 20 a |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
MTTFd | 11850 a |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 В°C (163.4 В°F) T5 : 88 В°C (190.4 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 69 В°C (156.2 В°F) T5 : 84 В°C (183.2 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW , T6 : 51 В°C (123.8 В°F) T5 : 66 В°C (150.8 В°F) T4 : 80 В°C (176 В°F) T3 : 80 В°C (176 В°F) T2 : 80 В°C (176 В°F) T1 : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW , T6 : 39 В°C (102.2 В°F) T5 : 54 В°C (129.2 В°F) T4 : 61 В°C (141.8 В°F) T3 : 61 В°C (141.8 В°F) T2 : 61 В°C (141.8 В°F) T1 : 61 В°C (141.8 В°F) |
Housing material | Crastin (PBTB), black |
Reduction factor rCu | 0.3 |
Connection type | cable silicone , 10 m |
Reduction factor r304 | 0.85 |
CE marking | [*PD-Z02586A*] |
Effective internal inductance | max. 200 andmicro;H A cable length of 10 m is considered. |
Diagnostic Coverage (DC) | 0 % |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
Degree of protection | IP68 |
Type of protection | intrinsic safety |
Use in the hazardous area | see instruction manuals |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
Type of protection | intrinsic safety |
Rated operating distance | 8 mm |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
Output type | 2-wire |
Switching function | Normally closed (NC) |
Effective internal inductance | max. 200 andmicro;H A cable length of 10 m is considered. |
EAC conformity | TR CU 012/2011 |
Effective internal inductance | max. 200 andmicro;H A cable length of 10 m is considered. |
Buy Pepperl+Fuchs NJ8-18GK-SN-10M-Y70101418 with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com offers electrical parts online. Our product range includes industrial sensors, motor control components, pneumatic automation, and many other automation equipment. We ship to any country as quickly as possible. By providing you with minimum prices, you can save money. You will be pleased to work with us. Our clients include a large number of well-known global manufacturing companies.