Pepperl+Fuchs OBD1100-R101-2EP-IO-IR Diffuse mode sensor

Pepperl+Fuchs OBD1100-R101-2EP-IO-IR
Item Number: OBD1100-R101-2EP-IO-IR
  • Miniature design with versatile mounting options
  • Extended temperature range
    -40В°C ... 60В°C
  • High degree of protection IP69K
  • IO-link interface for service and process data
  • Infrared light design
Price on Request
Quantity
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
Process data witdhProcess data input 1 Bit
Process data output 2 Bit
Signal output2 push-pull (4 in 1)outputs, short-circuit protected, reverse polarity protected, overvoltage protected
No-load supply current< 25 mA at 24 V supply voltage
Response time0.5 ms
Cable length2 m
Operating voltage10 ... 30 V DC
Detection range2 ... 1100 mm
Function indicatorLED yellow:
constantly on - object detected
constantly off - object not detected
Connection2 m fixed cable
Usage categoryDC-12 and DC-13
Operation indicatorLED green:
constantly on - power on
flashing (4Hz) - short circuit
flashing with short break (1 Hz) - IO-Link mode
Ambient light limitEN 60947-5-2
Communication interfaceIEC 61131-9
Device ID0x110101 (1114369)
Angle of divergence5.4 В°
Housing width13.9 mm
Mission Time (TM)20 a
SIO mode supportyes
Protection classIII
Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F) , fixed cable
-25 ... 60 В°C (-13 ... 140 В°F) , movable cable not appropriate for conveyor chains
Voltage drop 1.5 V DC
Switching currentmax. 100 mA , resistive load
MTTFd724 a
Switching voltagemax. 30 V DC
IO-Link Revision1.1
Control elementsLight-on/dark-on changeover switch
Adjustment range60 ... 1100 mm
LED risk group labellingexempt group
Detection range min.10 ... 60 mm
Light sourceLED
Compatible master port typeA
Light typemodulated infrared light 850 nm
Degree of protectionIP67 / IP69 / IP69K
Min. cycle time2.3 ms
Diameter of the light spotapprox. 100 mm at a distance of 1000 mm
Interface typeIO-Link ( via C/Q = BK )
Switching frequency1000 Hz
Diagnostic Coverage (DC)0 %
Massapprox. 10 g
Storage temperature-40 ... 70 В°C (-40 ... 158 В°F)
Product standardEN 60947-5-2
Switching typeThe switching type of the sensor is adjustable. The default setting is:
C/Q - BK: NPN normally open / light-on, PNP normally closed / dark-on, IO-Link
/Q - WH: NPN normally closed / dark-on, PNP normally open / light-on
UL approvalE87056 , cULus Listed , class 2 power supply , type rating 1
Housing depth18.3 mm
Ripplemax. 10 %
Housing height33.8 mm
Reference targetstandard white, 100 mm x 100 mm
Control elementsSensing range adjuster
Transfer rateCOM 2 (38.4 kBaud)

Comments

No comments yet

Write a comment

in international format without spaces