Pepperl+Fuchs R2-SP-IC*
Segment Protector for Cabinet Installation
- 4 ... 12 outputs Ex ic (FISCO or Entity) or non-incendive (Div 2)
- Advanced fault isolation at the spur
- Segment Protector in Zone 2/Div. 2
- Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
- For FOUNDATION Fieldbus H1 and PROFIBUS PA
- Advanced Diagnostics at the spur
- Power, Com, Diagnostics, and Error LEDs
- T-connector for easy installation and maintenance
- Test points for easy troubleshooting
Item Number:
R2-SP-IC*
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Connection type | pluggable , screw terminal or spring terminal |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Degree of protection | IEC 60529 |
Self current consumption | see table ""Technical data depending on model"" |
Shock resistance | 15 g 11 ms |
Fieldbus standard | IEC 61158-2 |
Design / Mounting | Cabinet installation |
Relative humidity | < 95 % non-condensing |
LED SPURS | red: 2 Hz flashing in short-circuit condition |
EU-Type Examination Certificate | TГњV 12 ATEX 098651 X |
Vibration resistance | EN 60068-2-6 |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
Shock resistance | EN 60068-2-27 |
Voltage drop trunk In/Out | 0 V |
IECEx approval | IECEx TUN 12.0015X |
Climatic conditions | IEC 60721 |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Marine approval | DNV A-14038 |
Ambient temperature | -50 ... 70 В°C (-58 ... 158 В°F) |
Terminating resistor | external type M-FT 100 andOmega; +/- 10 % |
UL approval | E326119 |
Electromagnetic compatibility | NE 21:2011 |
Switch | configuration of short-circuit current/rated current |
Vibration resistance | 1 g , 10 ... 150 Hz |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
Dimensions | see table ""Technical data depending on model"" |
Core cross-section | see table 2 |
Mass | see table ""Technical data depending on model"" |
Mounting | DIN rail mounting |
Housing material | Polycarbonate |
Degree of protection | IP20 |
Surge protection | Trunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V |
Storage temperature | -50 ... 85 В°C (-58 ... 185 В°F) |
Voltage drop main cable/outputs | max. 1.2 V |