Pepperl+Fuchs R8D0-MIO-Ex12.FF*
Multi-Input/Output Device for Cabinet Installation
- For discrete inputs and outputs
- Installation in Zone 1/Div. 1, intrinsically safe
- Sensors in Zone 0/Div. 1
- Connection to fieldbus acc. to FISCO or Entity
- For FOUNDATION Fieldbus H1
- PCS integration via device description and function blocks
- Monitors sensor condition
- Removable terminals
- Power, Com, Diagnostics, and Error LEDs
- Test points for easy troubleshooting
Item Number:
R8D0-MIO-Ex12.FF*
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
ITK version | 6.1.1 |
Number of outputs | 4 |
Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed |
Line fault detection | lead breakage , short circuit |
Electromagnetic compatibility | NE 21:2011 |
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
Line fault detection | lead breakage , short circuit (not in counter mode) |
Degree of protection | IP20 |
Supply current | 5 mA |
Relative humidity | 95 % non-condensing |
Switching frequency | min. 0.1 Hz max. 5 kHz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Implementation | resource block 1x RS function block 4x DO, 12x DI, 1x AI, 2x MDI, 1x MDO transducer block 4x TB |
Supply voltage | 6.6 V |
Fieldbus standard | IEC 61158-2 |
Pollution degree | 2 |
Supply current | 1.5 mA |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Rated current | max. 23 mA |
Vibration resistance | 5 g , 10 ... 150 Hz |
Input type | Frequency input / Counter Input , channel 1 |
Mounting | mounting on DIN rail in cabinet |
Galvanic isolation | EN 60079-11 |
Input type | Sensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable |
Number of inputs | 12 |
Shock resistance | 15 g , 11 ms |
LED CHANNEL ERROR | red, flashing: lead breakage/short circuit; off: no error |
Supply voltage | 5 V |
Polarity | not polarity sensitive |
Vibration resistance | EN 60068-2-6 |
FDE (Fault Disconnect Equipment) | 6.7 mA |
Fieldbus type | FOUNDATION Fieldbus |
LED PWR | green: on, bus voltage existent |
Number of inputs | 1 |
Degree of protection | IEC/EN 60529 |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Output type | Low power valve , channels 1, 4, 7, 10 |
IECEx approval | IECEx BVS 16.0051X |
LED COM ERR | red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error |
EU-Type Examination Certificate | BVS 16 ATEX E 075 X |
Marine approval | pending |
DIP switch | Address setting , write protection , simulation |
Pulse duration | min. 80 micro/s |
Design / Mounting | Cabinet installation |
Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) |
Housing material | Polycarbonate |
Ambient temperature | -50 ... 75 В°C (-58 ... 167 В°F) hazardous area -50 ... 85 В°C (-58 ... 185 В°F) safe area |
Mass | approx. 290 g |
Rated voltage | 9 ... 32 V |
Connection type | plug-in terminals , spring terminal and screw terminal |
Shock resistance | EN 60068-2-27 |