Pepperl+Fuchs R8D0-MIO-Ex12.FF*
Multi-Input/Output Device for Cabinet Installation

Pepperl+Fuchs R8D0-MIO-Ex12.FF*
  • For discrete inputs and outputs
  • Installation in Zone 1/Div. 1, intrinsically safe
  • Sensors in Zone 0/Div. 1
  • Connection to fieldbus acc. to FISCO or Entity
  • For FOUNDATION Fieldbus H1
  • PCS integration via device description and function blocks
  • Monitors sensor condition
  • Removable terminals
  • Power, Com, Diagnostics, and Error LEDs
  • Test points for easy troubleshooting
Item Number: R8D0-MIO-Ex12.FF*
1744.71
-
+
Total price: 1744.71
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
ITK version6.1.1
Number of outputs4
Input typeSensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed
Line fault detectionlead breakage , short circuit
Electromagnetic compatibilityNE 21:2011
Foundation Fieldbus/Field circuitsafe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V
Line fault detectionlead breakage , short circuit (not in counter mode)
Degree of protectionIP20
Supply current5 mA
Relative humidity 95 % non-condensing
Switching frequencymin. 0.1 Hz max. 5 kHz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Implementationresource block 1x RS
function block 4x DO, 12x DI, 1x AI, 2x MDI, 1x MDO
transducer block 4x TB
Supply voltage6.6 V
Fieldbus standardIEC 61158-2
Pollution degree2
Supply current1.5 mA
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Rated currentmax. 23 mA
Vibration resistance5 g , 10 ... 150 Hz
Input typeFrequency input / Counter Input , channel 1
Mountingmounting on DIN rail in cabinet
Galvanic isolationEN 60079-11
Input typeSensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable
Number of inputs12
Shock resistance15 g , 11 ms
LED CHANNEL ERRORred, flashing: lead breakage/short circuit; off: no error
Supply voltage5 V
Polaritynot polarity sensitive
Vibration resistanceEN 60068-2-6
FDE (Fault Disconnect Equipment)6.7 mA
Fieldbus typeFOUNDATION Fieldbus
LED PWRgreen: on, bus voltage existent
Number of inputs1
Degree of protectionIEC/EN 60529
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Output typeLow power valve , channels 1, 4, 7, 10
IECEx approvalIECEx BVS 16.0051X
LED COM ERRred, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error
EU-Type Examination CertificateBVS 16 ATEX E 075 X
Marine approvalpending
DIP switchAddress setting , write protection , simulation
Pulse durationmin. 80 micro/s
Design / MountingCabinet installation
Physical layer profileprofile type 511 (FISCO), profile type 111 (Entity)
Housing materialPolycarbonate
Ambient temperature-50 ... 75 В°C (-58 ... 167 В°F) hazardous area
-50 ... 85 В°C (-58 ... 185 В°F) safe area
Massapprox. 290 g
Rated voltage9 ... 32 V
Connection typeplug-in terminals , spring terminal and screw terminal
Shock resistanceEN 60068-2-27

Comments

No comments yet

Write a comment