Pepperl+Fuchs RD0-TI-Ex8.PA.*
Temperature Multi-Input Device for Cabinet Installation
We ship to United States of America!
- For 8 temperature or analog sensors
- Installation in Zone 1/Div. 1, intrinsically safe
- Sensors in Zone 0/Div. 1
- Connection to fieldbus acc. to FISCO or Entity
- For PROFIBUS PA
- DCS integration via GSD and FDT/DTM
- Monitors sensor condition
- For T/C, RTD 2-, 3-, 4-wire, voltage and resistance
- Cold junction compensation
- Removable terminals
Item Number:
RD0-TI-Ex8.PA.*
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Ambient temperature | -40 ... 70 ?°C (-40 ... 158 ?°F) hazardous area -40 ... 85 ?°C (-40 ... 185 ?°F) safe area |
Storage temperature | -40 ... 85 ?°C (-40 ... 185 ?°F) |
Vibration resistance | EN 60068-2-6 |
CSA approval | CoC 3025732C |
Rated voltage | 9 ... 32 V |
Rated current | max. 23 mA |
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Bus | FISCO see EC-Type Examination Certificate |
Design / Mounting | Cabinet installation |
Vibration resistance | 5 g , 10 ... 150 Hz |
Degree of protection | IEC 60529 |
FDE (Fault Disconnect Equipment) | 6.7 mA |
Fieldbus type | PROFIBUS PA |
Polarity | not polarity sensitive |
Marine approval | DNV A-14038 |
Galvanic isolation | EN 60079-11 |
Electromagnetic compatibility | NE 21:2011 |
Common mode voltage | Input to Input 600 Vpeak |
Mass | 360 g |
Firmware update | via separate plug connection |
Connection type | plug-in terminals , spring terminal and screw terminal |
Inputs | see EC-Type Examination Certificate |
Error detection | lead breakage, wiring error, hardware device error |
Number | 8 |
Sensor types | see table 1 |
LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange; off: no error |
Degree of protection | IP20 |
Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
Shock resistance | EN 60068-2-27 |
LED COM ERR | red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error |
Shock resistance | 15 g , 11 ms |
Housing material | Polycarbonate |
Internal measurement cycle | for all sensor types max. 1 s |
FM approval | CoC 3025732 |
Certificate | PTB 03 ATEX 2238 X |
Grounding | grounding of thermoelements possible |
Fieldbus standard | IEC 61158-2 |
Mounting | mounting on DIN rail in cabinet |
EU-Type Examination Certificate | PTB 03 ATEX 2237 |
LED PWR | green: on, bus voltage existent |
Relative humidity | 95 % non-condensing |
Buy Pepperl+Fuchs RD0-TI-Ex8.PA.* with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. delivers top-quality industrial control products. Our extensive inventory ensures you find the parts you need, with worldwide delivery options. We offer competitive prices and personalized service. Get in touch today to see how we can support your business effectively and efficiently.
People also buy
Comments
No comments yet