Pepperl+Fuchs S1SD-1DI-1R
Switch Amplifier

Pepperl+Fuchs S1SD-1DI-1R
  • 1-channel signal conditioner
  • 24 V DC supply
  • Input for 2- or 3-wire sensors or AC/DC voltage sources
  • Relay contact output
  • Timer function
  • Configurable by DIP switches
  • Connection via screw terminals
Item Number: S1SD-1DI-1R
131.00
-
+
Total price: 131.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Connectionterminals 3, 4:
Mechanical life107 switching cycles
Core cross-section0.5 ... 2.5 mm2 (20 ... 14 AWG)
Outputsignal, relay
Rated voltage16.8 ... 31.2 V DC
Optional accessoriespower feed module S1SD-2PF
Power Bus POWERBUS-SETL5.***
Power Bus POWERBUS-SETH5.***
cover for DIN mounting rail POWERBUS-COV.250
end cap POWERBUS-CAP
Energized/De-energized delay 20 ms / 20 ms
Power dissipation0.6 W
Control elementsDIP-switch
Configurationvia DIP switches
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Connectionscrew terminals
Output/power supplysafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min
Labelingspace for labeling at the front
Degree of protectionIEC 60529:2001
Degree of protectionIP20
Connection sidefield side
Massapprox. 60 g
Switching frequency 10 Hz
ConnectionPower Bus or terminals 1-, 2+
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connection sidecontrol side
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Signal typeDigital Input
Protection against electrical shockEN 61010-1:2010
Dimensions6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1
Contact loading253 V AC/2 A/cos andphi; > 0.7; 126.5 V AC/2 A/cos andphi; > 0.7; 30 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Power consumption1.1 W
Input/Other circuitssafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min

Comments

No comments yet