Pepperl+Fuchs SJ3,5-SN-Y89604
  • 3.5 mm slot width
  • Usable up to SIL 3 acc. to IEC 61508
Item Number: SJ3,5-SN-Y89604
98.04
-
+
Total price: 98.04
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Type of protectionintrinsic safety
Output type2-wire
CE marking[*PD-Z02586A*]
Housing materialPBT
Effective internal capacitancemax. 30 nF
A cable length of 10 m is considered.
Switching functionNormally closed (NC)
Output typeNAMUR with safety function
Switching frequency0 ... 3000 Hz
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 89 В°C (192.2 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 74 В°C (165.2 В°F)
Diagnostic Coverage (DC)0 %
Effective internal inductancemax. 100 µH
A cable length of 10 m is considered.
CE marking[*PD-Z02585A*]
Type of protectionintrinsic safety
Degree of protectionIP67
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 70 В°C (158 В°F)
T5 : 85 В°C (185 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 66 В°C (150.8 В°F)
T5 : 81 В°C (177.8 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 В°C (113 В°F)
T5 : 60 В°C (140 В°F)
T4 : 89 В°C (192.2 В°F)
T3 : 89 В°C (192.2 В°F)
T2 : 89 В°C (192.2 В°F)
T1 : 89 В°C (192.2 В°F)
at Ui = 20 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 30 В°C (86 В°F)
T5 : 45 В°C (113 В°F)
T4 : 74 В°C (165.2 В°F)
T3 : 74 В°C (165.2 В°F)
T2 : 74 В°C (165.2 В°F)
T1 : 74 В°C (165.2 В°F)
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 89 В°C (192.2 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 74 В°C (165.2 В°F)
CE marking[*PD-Z02585A*]
Safety Integrity Level (SIL)up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the ""exida Functional Safety Assessment"" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
Type of protectionintrinsic safety
Reference target10 x 7 x 0.3 mm3, Al
Safety Integrity Level (SIL)SIL 3
Type of protectionintrinsic safety
Connection typeflexible leads LiY , 150 mm
Mission Time (TM)20 a
Use in the hazardous areasee instruction manuals
UL approvalcULus Listed, General Purpose
Effective internal inductancemax. 100 µH
A cable length of 10 m is considered.
Effective internal capacitancemax. 30 nF
A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 В°C (163.4 В°F)
T5 : 88 В°C (190.4 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 66 В°C (150.8 В°F)
T5 : 81 В°C (177.8 В°F)
T4 : 100 В°C (212 В°F)
T3 : 100 В°C (212 В°F)
T2 : 100 В°C (212 В°F)
T1 : 100 В°C (212 В°F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 В°C (113 В°F)
T5 : 60 В°C (140 В°F)
T4 : 89 В°C (192.2 В°F)
T3 : 89 В°C (192.2 В°F)
T2 : 89 В°C (192.2 В°F)
T1 : 89 В°C (192.2 В°F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 30 В°C (86 В°F)
T5 : 45 В°C (113 В°F)
T4 : 74 В°C (165.2 В°F)
T3 : 74 В°C (165.2 В°F)
T2 : 74 В°C (165.2 В°F)
T1 : 74 В°C (165.2 В°F)
Ambient temperature-40 ... 100 В°C (-40 ... 212 В°F)
Effective internal capacitancemax. 30 nF
A cable length of 10 m is considered.
EMC in accordance withEN 60947-5-2:2007 + A1:2012
IEC 60947-5-2:2007 + A1:2012
MTTFd11800 a
Hysteresiswith NAMUR switch amplifier: 0.045 mm (e. g. Pepperl+Fuchs KCD2-SR-Ex1.LB)
with safety switch amplifier 0.025 mm (e. g. Pepperl+Fuchs KFD2-SH-Ex1)
Core cross-section0.14 mm2
Nominal voltage8.2 V
Effective internal inductancemax. 100 µH
A cable length of 10 m is considered.
Rate of current rise-4.5 mA / mm
Effective internal inductancemax. 100 µH
A cable length of 10 m is considered.
Equipment protection levelGb , Gc (ic) , Da , Mb
Slot width3.5 mm
Effective internal capacitancemax. 30 nF
A cable length of 10 m is considered.
Depth of immersion (lateral)5 ... 7 typ. 6 mm

Comments

No comments yet