Pepperl+Fuchs UC2500-F65-IE2R2-V15
Ultrasonic sensor
- Level indication
- 1 analog output, 4-20 mA current source
- 1 switch output
- Programmable by means of Interface (see accessories) and SONPROG
- Synchronization options
- Temperature compensation
Item Number:
UC2500-F65-IE2R2-V15
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Linearity error | 1.5 % |
Level | low level : 0 ... 3 V high level : 15 V |
Degree of protection | IP65 |
Dead band | 0 ... 250 mm |
Adjustment range | 250 ... 2500 mm |
Input voltage | Operating voltage |
CCC approval | CCC approval / marking not required for products rated 36 V |
Operating voltage | 15 ... 30 V (including ripple) In supply voltage interval 15 ... 20 V sensitivity reduced to 20% ... 0% |
Default setting | 250 ... 2500 mm |
Input type | 1 Function input |
UL approval | cULus Listed, General Purpose |
Output type | 1 current output 4 ... 20 mA , rising ramp |
Rated operating voltage | 24 V DC |
Sensing range | 250 ... 2500 mm |
Ripple | 10 % |
Connection type | Connector plug M12 x 1 , 5-pin |
Mass | 500 g |
Output type | 1 switch output PNP, NO |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Standard target plate | 100 mm x 100 mm |
Vibration resistance | 10 ... 55 Hz , Amplitude В± 1 mm |
Installation position | any position |
CSA approval | cCSAus Listed, General Purpose |
Shock resistance | 30 g , 11 ms period |
Time delay before availability | 250 ms |
Operating current | 300 mA , short-circuit/overload protected |
No-load supply current | 60 mA |
LED green | Power on |
LED yellow | solid: switching state switch output flashing: misadjustment |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Permissible cable length | max. 300 m |
Transducer frequency | approx. 120 kHz |
Default setting | 250 ... 2500 mm |
Voltage drop | 3 V |
Load resistor | 300 andOmega; |
People also buy
Comments