Pepperl+Fuchs VAA-2E-IER2-S-1M-V1

Read head and evaluation unit
Pepperl+Fuchs VAA-2E-IER2-S-1M-V1
Price on Request
One click request
IO code0
Degree of protectionIP67
UL File NumberE155795
Connectionwith fixed cable and M12 connector, 4-pin
Response delay< 5 ms
Slave typeSafety-Slave
Cable length1 m
Center offsetВ± 2.5 mm at distance s = 3 mm
Life span100 x 106 switching cycles
Performance level (PL)PL e
ID codeB
Mission Time (TM)20 a
AS-InterfaceEN 62026-2:2013
ID1 codeF
Detection typemagnetic
Rated operating current 30 mA
ProfileS-0.B
assured release distancemax. 40 mm
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Safety Integrity Level (SIL)SIL 3
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Functional safetyISO 13849-1:2008 (up to category 3/PL e) EN ISO 12100-1, -2:2003 EN 1088:1995+A2:2008
assured start-up distance7 mm
Power supplyvia AS-Interface network
Shock and impact resistance30 g/11 ms
ID2 codeE
PFHd4.29 E-8
Required master specification V2.0
AS-Interface specificationV2.1
Data bits (function via AS-Interface)Input
Installationany position
Degree of protectionEN 60529:2000
in international format without spaces